15
Input Power and Motor Cable Stripping Lengths
Power Wiring in Inches (mm)
Motor Wiring in Inches(mm)
Size
A1
B1
C1
D1
A2
B2
C2
D2
FR1
0.39
1.77
0.39
1.38
0.39
1.77
0.39
1.38
(10)
(45)
(10)
(35)
(10)
(45)
(10)
(35)
FR2
0.59
1.77
0.59
1.77
0.59
1.57
0.59
1.57
(15)
(45)
(15)
(45)
(15)
(40)
(15)
(40)
FR3
0.59
1.57
0.59
1.97
0.59
1.57
0.59
1.97
(15)
(40)
(15)
(50)
(15)
(40)
(15)
(50)
FR4
0.98
2.56
0.98
4.72
0.98
2.56
0.98
4.72
(25)
(65)
(25)
(120)
(25)
(65)
(25)
(120)
FR5
1.10
6.10
1.10
9.45
1.10
6.10
1.10
9.45
(28)
(155)
(28)
(240)
(28)
(155)
(28)
(240)
FR6
0.98
4.72
0.98
7.87
0.98
4.72
0.98
7.87
(25)
(120)
(25)
(200)
(25)
(120)
(25)
(200)
Power Connection Tightening Torque
Frame
Size
Power wire
in-lb (Nm)
Ground
wire
in-lb (Nm)
Control wire
in-lb (Nm)
@
FR1
5.3 (0.6)
10 (1.1)
4.5 (0.5)
FR2
15.6 (1.8)
10 (1.1)
4.5 (0.5)
FR3
40 (4.5)
10 (1.1)
4.5 (0.5)
FR4
95 (10.7)
14 (1.6)
4.5 (0.5)
FR5
354 (40.0)
35 (4.0)
4.5 (0.5)
FR6
480 (54.2)
35 (4.0)
4.5 (0.5)
Notes:
-
Strip the motor and power cables as shown above.
-
Both UL and IEC tools may be used
-
Applies to strained wire, solid wire, or ferrule installations
Summary of Contents for EVH Series
Page 1: ...Copeland Commercial HVACR Variable Frequency Drive EVH Series Installation Manual ...
Page 5: ...5 Rating Label Carton Label Keypad Button Overview ...
Page 13: ...13 Rubber Grommet Installation Instructions Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 ...
Page 31: ...31 Step 3 Control Board Layout ...
Page 37: ...37 H1 H1S Approximate dimensions in inches mm ...
Page 38: ...38 H2 H2S Approximate dimensions in inches mm ...
Page 39: ...39 H3 H3X IP54 Approximate dimensions in inches mm ...
Page 40: ...40 H4 CX IP54 Approximate dimensions in inches mm ...
Page 41: ...41 DX IP21 DX IP54 Approximate dimensions in inches mm ...
Page 44: ...44 ...
Page 45: ...45 ...