2
3
International cable and fuse sizes—208 Vac to 240 Vac Ratings
Notes:
-
Line and motor cable size is selected according to IEC 60364-5-52:2009 Table B.52.4 for copper
conductor with PVC insulation with a wiring condition of ambient temperature 30 °C in air and an
installation method of “B2” (cables in conduit and cable trunking systems). For other wiring conditions,
please refer to the standard of IEC 60364-5-52:2009 for suitable cable sizes.
-
Earthing conductor size is determined by the cross-sectional area of phase conductors according to
IEC/EN 61800-5-1:2007 Table 5. So, if phase conductor size is changed, earthing conductor size should
also be changed accordingly.
-
If power cubes or bypass are used, a Class gG/gL fuse is recommended.
Frame
size
208 V
input
current
(VT/IL)
Current
(VT/IL)
at 40 °C
Fuse
rating
(gG/gL)
Mains and
motor
cable
Cu (mm2)
Terminal cable size
Main
terminal
Cu (mm2)
Earth
terminal
Cu (mm2)
FR1
4.4
4.8
6
3*1.5+1.5
0.2–6 solid or
0.2–4 stranded
0.75–6
6.1
6.6
10
3*1.5+1.5
0.2–6 solid or
0.2–4 stranded
0.75–6
7.2
7.8
16
3*1.5+1.5
0.2–6 solid or
0.2–4 stranded
0.75–6
10.2
11
16
3*1.5+1.5
0.2–6 solid or
0.2–4 stranded
0.75–6
11.6
12.5
16
3*1.5+1.5
0.2–6 solid or
0.2–4 stranded
0.75–6
FR2
16.3
17.5
20
3*4+4
0.5–16
4–16
23.2
25
32
3*4+4
0.5–16
4–16
29
31
32
3*6+6
0.5–16
4–16
FR3
44.2
48
50
3*16+16
16–35
2.5–25
56
61
63
3*16+16
16–35
2.5–25
FR4
64.6
75
80
3*25+16
16–50
6–50
78
88
100
3*35+16
16–50
6–50
94.3
114
125
3*50+25
16–50
6–50
FR5
129
143
160
3*70+35
50–185
10–120
157
170
200
3*95+50
50–185
10–120
189
211
250
3*150+95
50–185
10–120
FR6
242.8
261
400
2*(3*70+35)
2*(50–150)
35–150
290.3
312
400
2*(3*95+50)
2*(50–150)
35–150
Summary of Contents for EVH Series
Page 1: ...Copeland Commercial HVACR Variable Frequency Drive EVH Series Installation Manual ...
Page 5: ...5 Rating Label Carton Label Keypad Button Overview ...
Page 13: ...13 Rubber Grommet Installation Instructions Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 ...
Page 31: ...31 Step 3 Control Board Layout ...
Page 37: ...37 H1 H1S Approximate dimensions in inches mm ...
Page 38: ...38 H2 H2S Approximate dimensions in inches mm ...
Page 39: ...39 H3 H3X IP54 Approximate dimensions in inches mm ...
Page 40: ...40 H4 CX IP54 Approximate dimensions in inches mm ...
Page 41: ...41 DX IP21 DX IP54 Approximate dimensions in inches mm ...
Page 44: ...44 ...
Page 45: ...45 ...