2
5
International cable and fuse sizes—380 Vac to 440 Vac ratings
Terminal cable size
Frame size
Amp
suffix
400 V input
current
(VT/I
L
)
Current
(VT/I
L
)
at 40 °C
Fuse
rating
(gG/gL)
@
Mains and motor
cable Cu (mm
2
)
Main terminal
Cu (mm
2
)
Earth terminal
Cu (mm
2
)
FR1
3D3
3.1
3.3
6
3*1.5+1.5
0.2–6 solid or
0.75–6
4D3
4
4.3
6
3*1.5+1.5
0.2- 4 standard
0.75–6
5D6
5.2
5.6
10
3*1.5+1.5
0.75–6
7D6
7.1
7.6
16
3*1.5+1.5
0.75–6
9D0
8.4
9
16
3*1.5+1.5
0.75–6
012
11.2
12
16
3*1.5+1.5
0.75–6
FR2
016
15
16
20
3*4+4
0.5–16
4–16
023
21.5
23
25
3*4+4
0.5–16
4–16
031
29
31
32
3*6+6
0.5–16
4–16
FR3
038
35.2
38
40
3*16+16
16–35
2.5–25
046
42.6
46
50
3*16+16
16–35
2.5–25
061
55.7
61
63
3*16+16
16–35
2.5–25
FR4
072
65.7
72
80
3*25+16
16–50
6–50
087
79.4
87
100
3*35+16
16–50
6–50
105
97
105
125
3*50+25
16–50
6–50
FR5
140
129
140
160
3*70+35
50–185
10–120
170
157
170
200
3*95+50
50–185
10–120
205
189
205
250
3*120+70
50–185
10–120
FR6
261
246.2
261
400
2*(3*70+35)
2*(50–150)
35–150
310
292.4
310
400
2*(3*95+50)
2*(50–150)
35–150
Notes:
-
Line and motor cable size is selected according to IEC 60364-5-52:2009 Table B.52.4 for copper conductor
with PVC insulation with a wiring condition of ambient temperature 30 °C in air and an installation method of
“B2” (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the standard
of IEC 60364-5-52:2009 for suitable cable sizes.
-
Earthing conductor size is determined by the cross-sectional area of phase conductors according to
IEC/EN 61800-5-1:2007 Table 5. So, if phase conductor size is changed, earthing conductor size should
also be changed accordingly.
-
If power cubes or bypass are used, a Class gG/gL fuse is recommended.
Summary of Contents for EVH Series
Page 1: ...Copeland Commercial HVACR Variable Frequency Drive EVH Series Installation Manual ...
Page 5: ...5 Rating Label Carton Label Keypad Button Overview ...
Page 13: ...13 Rubber Grommet Installation Instructions Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 ...
Page 31: ...31 Step 3 Control Board Layout ...
Page 37: ...37 H1 H1S Approximate dimensions in inches mm ...
Page 38: ...38 H2 H2S Approximate dimensions in inches mm ...
Page 39: ...39 H3 H3X IP54 Approximate dimensions in inches mm ...
Page 40: ...40 H4 CX IP54 Approximate dimensions in inches mm ...
Page 41: ...41 DX IP21 DX IP54 Approximate dimensions in inches mm ...
Page 44: ...44 ...
Page 45: ...45 ...