Operating instruction 

EC3-D7x Digital Superheat Controller 

EC3-D72 with TCP/IP communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 18.07.2017 

EC3-D7x_OI_ML_R06_865019.docx 

P r e p a r a t i o n   f o r   S t a r t - u p :  

 

Vacuum the entire refrigeration system. 

 

Note:

  EMERSON  Electrical Control Valves EX4-6  are delivered at half open 

position. Do not charge system before closure of valve. 

 

Apply supply voltage 24 V to EC3 while the digital input is 0 V (open). The valve 
will be driven to close position. 

 

After closure of valve, start to charge the system with refrigerant. 

 

Start the system and check the superheat and operating conditions. 

 

E C D - 0 0 2   d i s p l a y / k e y p a d   u n i t :   ( L E D s   a n d   b u t t o n   f u n c t i o n s )  

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

P r o c e d u r e   f o r   p a r a m e t e r   m o d i f i c a t i o n   u s i n g   E C D - 0 0 2 :  

 

Note:

  Some of the functions/parameters (manual control and TCP/IP 

configuration) cannot be modified when using ECD-002 comparing to a set-up by 
PC via TCP/IP. 

 

 

Warning: 

 

All alarms are disabled during manual control. We do not recommend 
unattended operation of system during manual control.

 

 

The parameters can be accessed via the 4-button keypad. The configuration 
parameters are protected by a numerical password. The default password is “12”. 
To select the parameter configuration: 

 

Press the 

PRG

 button for more than 5 seconds, a flashing “0” is displayed 

 

Press 

 or 

 until “12” is displayed (password) 

 

Press 

SEL

 to confirm password 

 

Press 

 or 

 to show the code of the parameter that must be changed; 

 

Press 

SEL

 to display the selected parameter value;  

 

Press 

 or 

 to increase or decrease the value; 

 

Press 

SEL

 to temporarily confirm the new value and display its code;  

 

Repeat the procedure from the beginning "

press  

 or 

 

to show...

 

To exit and save the new settings: 

Press 

PRG 

to confirm the new values and exit 

the parameters modification procedure. 

 

To exit without modifying any parameters: 

Do not press any button for at least 

60 seconds (TIME OUT). 

 

S p e c i a l   F u n c t i o n s :  

The Special Functions can be activated by:

 

 

Press 

 and 

 together for more than 5 seconds, a flashing “0” is displayed. 

 

Press 

 or 

 until the password is displayed (default = “12”).  

If password was changed, select the new password. 

 

Press 

SEL

 to confirm password 

A “0” is displayed and the Special Function mode is activated. 

 

Press 

 or 

 to select the function. The number of special functions is dynamic 

and controller dependent. See list below. 

0: 

Reset controller to factory settings (this action is possible only when  

   

digital input is 0 V i.e. open). 

1:  

Displays the current TCP/IP address. 

2:  

Assign temporary 192.168.1.101 as TCP/IP address if EC3-D72x has  

   

different address. 

 

Press 

SEL

 to activate the function without leaving the special function mode. 

 

Press 

PRG

 to activate the function and leave the special function mode. 

M a i n   p a r a m e t e r s :    
(must be checked and modified if necessary) 

Code 

Parameter description and choices 

Min

 

Max

 

Factory 

setting

 

Field 

setting 

H5  Password 

199 

12 

 

u0  System refrigerant 

15 

 

 

0 = R22    

1 = R134a   

2 = R507   3 = R404A 4 = R407C  

5 = R410A  

6 = R124  7 = R744 (subcritical application) 

8 = R407A  

9 = R407F  

10 = R32

*  

11 = R448A 

 

12 = R449A 

13 = R450A 

14 = R513A 

15 = R1234ze

 

 

uP  Installed pressure sensor type 

2  

 

 

0 = PT5-07x (for R22 / R134a / R507 / R404A / R407A / R407C /  
 

 

      R407F / R124 / R448A /R449A / R450A / R513A /  

 

 

      R1234ze) 

1 = PT5-18x (for R410A/ R32) 
2 = PT5-30x (for R410A / R744 / R32)

 

 

ut 

Installed valve type 

 

 

1 = EX4    

2 = EX5    

3 = EX6  

 

 

uu  Start valve opening (%) 

10 

100 

50 

 

u9  Start opening duration (second) 

30 

 

uL  Low superheat alarm function 

 

 

0 = disable (for flooded evaporator)   
1 = enable auto reset 

2 = enable manual reset 

Cut-out at 0.5K (if it maintains 1 min.); Cut-in immediately at 3K 

 

u5  Superheat set-point (K) 

If uL enabled (auto or manual) 
If uL disabled 

 

0.5 

 

30 
30 

 


 
 

u2  MOP function 

 

 

0 = disable      1 = enable 

 

u3  MOP set-point (°C) saturation temperature 

** 

 

 

**) Factory setting is according to selected refrigerant (u0): 

+13°C - R22 

+15°C - R134a 

 

  +7°C - R507 

  +7°C - R404A 

+15°C - R407C 

 

+15°C - R410A 

+50°C - R124 

   -5°C - R744 

 

+10°C - R407A   

+10°C - R407F 

+10°C - R32  

 

+12°C - R448A 

+12°C - R449A 

+19°C - R450A 

 

+13°C - R513A  

+24°C - R1234ze 

*) Min. and Max. setting values are dependent to selected type of 
refrigerant 

 

┌┘

5  Units conversion  

 

 

0 = °C, K, bar   

1 = °F, R, psig 

(Psig values are divided by 10. Example: Display 12.5 is 125 psig) 

 

┌┘

1  Value to show 

 

0 = Measured superheat (K)   1 = Measured evaporating pressure, (bar); 
2 = Valve opening (%)   

3 = Measured coil-out temperature (°C) 

4 = Calculated evaporating temperature (°C) from the pressure  

5 = Compressor capacity in % 

 

u4  Superheat control mode 

 

 

0 = Standard,     1 = Slow,  

uH  High superheat alarm function 

0 = disable,     1 = enable auto reset 

 

 

 

uA  High superheat alarm setpoint 

16 

40 

30 

 

ud  High superheat alarm delay, min. 

15 

 

P2  Freeze protection cut-out, °C 

-40 

40 

 

P3  Freeze protection cut-in, °C 

-37 

43 

 

P4  Freeze protection alarm function 

0 = disable,      1 = enable auto-reset,   
2 = enable manual reset) 

 

P5  Freeze protection alarm delay, sec. 

199 

30 

 

P6  Pump-down function 

(0 = disable,     1 = enable auto-reset) 

 

P7   Pump-down cut-out, barg 

-0,5 

18 

0.5 

 

P8  Pump-down time delay, sec. 

199 

30 

 

P9  Low pressure alarm function 

(0 = disable,     1 = enable auto-reset, 
 2 = enable manual reset) 

 

PA  Low pressure alarm cut-out, barg 

-0,8  17,7 

 

Pb  Low pressure alarm delay, sec. 

199 

 

Pd  Low pressure alarm cut-in, barg 

-0,5 

18 

0.3 

 

L2  Output logic 

 

 

0: Alarm = normal, pump down. = normal 
1: Alarm = inverse, pump down. = normal 
2: Alarm = normal, pump down. = inverse 
3: Alarm = inverse, pump down. = inverse

 

 

 

 

 

 

Blinking:

 valve is closing 

ON:

 valve is fully close 

Blinking:

 valve is opening 

ON:

 valve is fully open 

ON

: demand 

OFF

: no demand 

Blinking

: pump 

down 
 

ON

: alarm 

OFF

: no alarm 

Parameters setting/saving 

Selecting/confirming 

Next parameter/ 
value (higher) 

Next parameter/ 
value (lower) 

Prg&Sel (5 sec) 
Manual reset for 
blinking alarm codes 

Summary of Contents for EC3-D72

Page 1: ...efer to the electrical wiring diagram for electrical connections Do not apply voltage to the controller before completion of wiring Ground the metal housing with a 6 3 mm spade connector Keep controller and sensor wiring well separated from mains wiring Minimum recommended distance 30 mm Use a class II category transformer for 24 VAC power supply Do not ground the 24 VAC lines We recommend using i...

Page 2: ...eave the special function mode Main parameters must be checked and modified if necessary Code Parameter description and choices Min Max Factory setting Field setting H5 Password 1 199 12 u0 System refrigerant 0 15 1 0 R22 1 R134a 2 R507 3 R404A4 R407C 5 R410A 6 R124 7 R744 subcritical application 8 R407A 9 R407F 10 R32 11 R448A 12 R449A 13 R450A 14 R513A 15 R1234ze uP Installed pressure sensor typ...

Page 3: ...that digital input is 0V open turn the power supply ON Four parameters i e refrigerant type u0 pressure sensor type uP valve type ut and control mode can be set only when digital input is open 0V while the power supply is ON 24 V This feature is for added safety to prevent accidental damage of compressors and other system components All other parameters can be modified at any time The EC3 D72 has ...

Page 4: ...g Fully close Pumpdown deactivated Check the system No Fixed differential 10 C Er Data error display out of range Data send to the display is out of range Check temperature and pressure sensor No No data to display Check Cable and plug connection between EC3 D7 and ECD 002 No Note When multiple alarms occur the highest priority alarm is displayed until being cleared then the next highest alarm is ...

Page 5: ...ary connection EXV control loop remains active when input is 24 V and the digital scroll is idle NTC input Coil out temperature sensor EMERSON temperature sensor ECN Nxx ECN Pxx NTC input Discharge temperature sensor Copeland NTC 86 kOhm at 25 C 4 20 mA Analog input EMERSON PT5 Pressure Transmitter 4 20 mA Analog output Deviation from input signal For connection to any 3rd party controller with 12...

Page 6: ...ngsschema durchführen Versorgungsspannung erst nach kompletter Installation anlegen Gehäuse mit einem 6 3 mm Flachstecker erden Signalleitungen und Leitungen mit Netzspannung in getrennten Kabelschächten verlegen Mindestabstand 30 mm Für die 24 V Stromversorgung sind ausschließlich Transformatoren der Klasse II zu verwenden Die 24 V Leitungen dürfen nicht geerdet werden Wir empfehlen die Verwendun...

Page 7: ...h und reglerabhängig 0 Regler auf Werkseinstellung zurücksetzen Reset nur bei offenem Digitaleingang O V möglich 1 Aktuelle TCP IP Adresse anzeigen 2 Dem Regler vorübergehend die Standard TCP IP Adresse 192 168 1 101 zuweisen falls dieser eine andere Adresse besitzt Nach dem Abschalten wird die zuvor eingestellte Adresse wieder aktiviert SEL drücken alle Parameter werden auf Werkseinstellung zurüc...

Page 8: ...einstellung und Datenanzeige auf Webseiten empfohlene Methode Während am Digitaleingang 0V anliegen Versorgungsspannung anschalten Die vier Parameter Kältemittel u0 Drucksensor Typ uP Ventil Typ ut und Kontrollmode können nur eingestellt werden wenn der Digitaleingang offen 0 V und die Versorgungsspannung AN 24 V ist Diese Sicherheitsfunktion verhindert die Beschädigung des Verdichters oder andere...

Page 9: ...Fehler überprüfen Nein Feste Differenz 10 C Er Daten außerhalb des Anzeigebereichs Display kann Daten nicht darstellen Einstellwert der Parameter verändern Nein Keine Daten Kable und Steckerverbindungen zwischen EC3 D7 und ECD 002 prüfen Nein Hinweis Bei mehreren Alarmen gleichzeitig wird der Alarm mit der höchsten Priorität angezeigt nach dessen Beseitigung wird der nächsthöhere angezeigt usw bis...

Page 10: ... DC zum Anschluss eines Hilfskontaktes Bei 24 V bleibt das EX Ventil aktiv auch wenn der Digital Scroll im Leerlauf arbeitet NTC Analogeingang EMERSON Temperatursensor ECN N60 ECN P60 NTC Analogeingang für Sensor Austrittstemperatur Copeland NTC 86 kOhm bei 25 C 4 20 mA Analogeingang EMERSON PT5 Drucktransmitter 4 20 mA Analogausgang Abweichung vom Eingangssignal für externen Regler mit 12 24 VDC ...