Operating instruction 

EC3-D7x Digital Superheat Controller 

EC3-D72 with TCP/IP communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 18.07.2017 

EC3-D7x_OI_ML_R06_865019.docx 

T e c h n i c a l   d a t a  

Power supply 

24 VAC ±10%; 50/60 Hz; 1 A 

Power consumption 

25 VA max. including EX4-6 

Plug-in connector 

Removable screw terminals 
wire size 0.14…1.5 mm

2

 

Grounding 

6.3 mm spade earth connector 

Protection class 

IP20 

COM, TCP/IP connection 

RJ45 Ethernet 

Connection to optional ECD-002 

ECC-Nxx or CAT5 cable with RJ45 connectors 

Digital Input; Cooling demand 

0/24 VAC/DC for stop/start function  
EX valve closes during stop command. Typically thermostat or third party controller. 

Digital Input; Comp2 running 

0/24 VAC/DC typically connected to auxiliary connection  
EXV control loop remains active when input is 24 V and the digital scroll is idle. 

NTC input; Coil-out temperature sensor 

EMERSON temperature sensor ECN-Nxx/ECN-Pxx  

NTC input; Discharge temperature sensor 

Copeland® NTC 86 kOhm at +25 °C 

4-20 mA Analog input 

EMERSON PT5 Pressure Transmitter 

4-20 mA Analog output 
 
Deviation from input signal 

For connection to any 3

rd

 party controller with 12/24 VDC power supply and appropriate burden 

 
±8% max 

Output alarm relay 
(If L2 = 1) 

Activated: 

 

 

 

Deactivated: 

SPDT contacts 24 VAC/DC, 2 A inductive load 
During normal operation (no alarm condition) 
During alarm condition or power supply is OFF 

Output pump down relay 
(If L2 = 1) 

Activated: 

 

 

 

Deactivated 

SPDT contact 24 VAC/DC, 2 Amp inductive load 
During normal operation 
All other conditions 

Output Digital Scroll Triac 

24 V or 230 V AC output to activate PWM valve on Digital Scroll 

Ambient temperature range 

  0…+60°C 
+1…+25°C (for best battery life time) 
> 35°C battery life time < 2 years 

Marking 

  

 
 
 

D i m e n s i o n s   [ m m ] :  

 

     

 

 

EC3-D7x 

 

 

 

 

 

 

 

 

 

 

 

ECD-002 

 
 
 
 
 

 

Summary of Contents for EC3-D72

Page 1: ...efer to the electrical wiring diagram for electrical connections Do not apply voltage to the controller before completion of wiring Ground the metal housing with a 6 3 mm spade connector Keep controller and sensor wiring well separated from mains wiring Minimum recommended distance 30 mm Use a class II category transformer for 24 VAC power supply Do not ground the 24 VAC lines We recommend using i...

Page 2: ...eave the special function mode Main parameters must be checked and modified if necessary Code Parameter description and choices Min Max Factory setting Field setting H5 Password 1 199 12 u0 System refrigerant 0 15 1 0 R22 1 R134a 2 R507 3 R404A4 R407C 5 R410A 6 R124 7 R744 subcritical application 8 R407A 9 R407F 10 R32 11 R448A 12 R449A 13 R450A 14 R513A 15 R1234ze uP Installed pressure sensor typ...

Page 3: ...that digital input is 0V open turn the power supply ON Four parameters i e refrigerant type u0 pressure sensor type uP valve type ut and control mode can be set only when digital input is open 0V while the power supply is ON 24 V This feature is for added safety to prevent accidental damage of compressors and other system components All other parameters can be modified at any time The EC3 D72 has ...

Page 4: ...g Fully close Pumpdown deactivated Check the system No Fixed differential 10 C Er Data error display out of range Data send to the display is out of range Check temperature and pressure sensor No No data to display Check Cable and plug connection between EC3 D7 and ECD 002 No Note When multiple alarms occur the highest priority alarm is displayed until being cleared then the next highest alarm is ...

Page 5: ...ary connection EXV control loop remains active when input is 24 V and the digital scroll is idle NTC input Coil out temperature sensor EMERSON temperature sensor ECN Nxx ECN Pxx NTC input Discharge temperature sensor Copeland NTC 86 kOhm at 25 C 4 20 mA Analog input EMERSON PT5 Pressure Transmitter 4 20 mA Analog output Deviation from input signal For connection to any 3rd party controller with 12...

Page 6: ...ngsschema durchführen Versorgungsspannung erst nach kompletter Installation anlegen Gehäuse mit einem 6 3 mm Flachstecker erden Signalleitungen und Leitungen mit Netzspannung in getrennten Kabelschächten verlegen Mindestabstand 30 mm Für die 24 V Stromversorgung sind ausschließlich Transformatoren der Klasse II zu verwenden Die 24 V Leitungen dürfen nicht geerdet werden Wir empfehlen die Verwendun...

Page 7: ...h und reglerabhängig 0 Regler auf Werkseinstellung zurücksetzen Reset nur bei offenem Digitaleingang O V möglich 1 Aktuelle TCP IP Adresse anzeigen 2 Dem Regler vorübergehend die Standard TCP IP Adresse 192 168 1 101 zuweisen falls dieser eine andere Adresse besitzt Nach dem Abschalten wird die zuvor eingestellte Adresse wieder aktiviert SEL drücken alle Parameter werden auf Werkseinstellung zurüc...

Page 8: ...einstellung und Datenanzeige auf Webseiten empfohlene Methode Während am Digitaleingang 0V anliegen Versorgungsspannung anschalten Die vier Parameter Kältemittel u0 Drucksensor Typ uP Ventil Typ ut und Kontrollmode können nur eingestellt werden wenn der Digitaleingang offen 0 V und die Versorgungsspannung AN 24 V ist Diese Sicherheitsfunktion verhindert die Beschädigung des Verdichters oder andere...

Page 9: ...Fehler überprüfen Nein Feste Differenz 10 C Er Daten außerhalb des Anzeigebereichs Display kann Daten nicht darstellen Einstellwert der Parameter verändern Nein Keine Daten Kable und Steckerverbindungen zwischen EC3 D7 und ECD 002 prüfen Nein Hinweis Bei mehreren Alarmen gleichzeitig wird der Alarm mit der höchsten Priorität angezeigt nach dessen Beseitigung wird der nächsthöhere angezeigt usw bis...

Page 10: ... DC zum Anschluss eines Hilfskontaktes Bei 24 V bleibt das EX Ventil aktiv auch wenn der Digital Scroll im Leerlauf arbeitet NTC Analogeingang EMERSON Temperatursensor ECN N60 ECN P60 NTC Analogeingang für Sensor Austrittstemperatur Copeland NTC 86 kOhm bei 25 C 4 20 mA Analogeingang EMERSON PT5 Drucktransmitter 4 20 mA Analogausgang Abweichung vom Eingangssignal für externen Regler mit 12 24 VDC ...

Reviews: