1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX
20/40
P1E
End of scaling for pressure transducer P1:
(P1i to 99.9 bar; P1i to 999 PSI) it is
the pressure value measured from sensor corresponding to
4.5V
P1F
Pressure transducer P1 calibration:
depending on the type of sensor as follow
P1C=0-5
-12.0 to 12.0 bar; -200 to 200 PSI
P1C=ntC
-12.0 to 12.0°C; -21 to 21°F
P1d
Pressure probe P1 reading error delayed (valid if P1C=0-5):
0 to 255 min
15.3.2
Condensing Probe Configuration
P2P
Condensing probe P2: n
=not available (regulation disabled);
Y
=available
(regulation enabled)
P2C
Condensing transducer configuration:
0-5
= ratiometric transducer (5.0Vdc)
ntC
=temperature probe NTC 10k
P2i
Start of scaling for pressure transducer P2:
(-1.5 to P2E bar; -21 to P2E PSI) it
is the pressure value measured from sensor corresponding to
0.5Vdc
P2E
End of scaling for pressure transducer:
(P2i to 99.9 bar; P2i to 999 PSI) it is the
pressure value measured from sensor corresponding to
4.5V
P2F
Pressure transducer calibration:
depending on the type of sensor as follow
P2C=0-5
-12.0 to 12.0 bar; -200 to 200 PSI
P2C=ntC
-12.0 to 12.0°C; -21 to 21°F
P2d
Pressure probe reading error delayed (valid if P2C=0-5):
0 to 255 min
15.3.3
Other Probes Configuration
P3P
Probe P3 presence: n
=not available;
Y
=available
P3C
Probe P3 configuration(*)
n86
=temperature probe NTC86k
ntC
=temperature probe NTC10k
Pt1
=temperature probe PT1000
P3F
Calibration:
-12.0 to 12.0°C; -21 to 21°F
P4P
Probe P4 presence: n
=not available;
Y
=available
P4C
Probe P4 configuration(*)
n86
=temperature probe NTC86k
ntC
=temperature probe NTC10k
Pt1
=temperature probe PT1000
P4F
Calibration:
-12.0 to 12.0°C; -21 to 21°F
dEr
Delay before activating probe error:
0 to 255 sec
(*)The support of the various types of probes depends on the model.
15.4 DISPLAY
Unt
Unit of measurement for pressure:
bar, PSI
CF
Unit of measurement for temperature:
°C
=Celsius degree;
°F
=Fahrenheit degree
dLY
Delayed visualization:
0 to 255 sec
Lod
Variable visualization: P1
;
P2
;
P3
;
St1
=SETPOINT1 value;
St2
=SETPOINT2
value;
PEr
=TRIAC activation in percentage;
Aou
=analogue output in percentage
15.5 COMPRESSOR CONFIGURATION
CPb
Compressor regulation probe:
nP; P1; P2; P3; P4
rtY
Type of regulation: db
=dead band;
PrP
=proportional band
CPo
Compressor power (valid for tandem units): SPo
=same power;
dPo
= different
power