16.5.3
ELECTRONIC VENTILATORS
If par.
oAn=EFn
, then the analogue output can be used to control electronic ventilators (with
input signal command 0-10Vdc). Regulation is proportional in the band defined from par.
HY2
:
-
When
VAL=St2
the analogue output will be forced to
Ao1
-
When
St2 < VAL < St2+HY2
the analogue output will be proportional in the range
Ao1...Ao2
-
When
VAL >= St2+HY2
the analogue output will be forced to
Ao2
16.5.4
SILENT MODE
The activation of the silent mode reduces the maximum allowed speed for ventilators when in
predefined intervals.
Parameter Description
FSS
Fan speed when silent mode active
Hd1
First holyday of the week
Hd2
Second holyday of the week
iLE
Beginning of the silence mode interval during working days
dLE
Duration of the silence mode interval during working days
iSE
Beginning of the silence mode interval during holydays
dSE
Duration of the silence mode interval during holydays