1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX
26/40
oAn
Analogue output:
-
nu
=output not used
-
onF
=output activated when controller in ON
-
ALr
=alarm output
-
EFn
=electronic ventilator control
-
PrP
=analogue repeater
-
inV
=inverter-controlled compressor output
bEn
Buzzer enabled:
n; Y
15.16 DIGITAL INPUTS
Digital inputs 1 and 3 depend on the presence of probe P3 and P4 respectively. Digital input 2 is
always available.
ixF
Digital input function (x=1, 2, 3):
nu
=not used
Enb
=enabling regulation signal
LP
=external low pressure alarm
HP
=external high pressure alarm
ES
=energy saving mode activation and deactivation
SiL
=silent mode activation and deactivation
EAL
=external alarm (warning)
bAL
=external alarm (lockout)
oAx
=output
oAx
(x=1, 2, 3, n) deactivation
rEV
=inversion for analogue output (
oAn=PrP
)
ixP
Digital input polarity (x=1, 2, 3)
oP
= active when contact is open
CL
= active when contact is closed
dxd
Activation delay for digital input (x=i, 2, 3):
0 to 255 min
nPx
Max number of external alarm events, detected from a digital input, before
stopping the regulation (x=1, 2, 3):
(0 to 15) if
ixF=LP
,
HP
or
bAL
, after detecting
nPx
alarms in an interval of time
diA
, the regulation will be stopped.
diA
Interval of time for LP, HP, bAL lockout alarm management:
0 to 100 hours.
When
diA=0
this function is disabled.
HPF
Minimum time with compressor locked in case of LP, HP, bAL lockout alarms:
0 to 15 min
Ar
Regulation restart in case of any lockout alarm:
MAn
=manual, a power-off and
power-on is required;
Aut
=automatic after resetting the alarm condition
15.17 OTHER
Adr
Serial address:
1 to 247
Hur
Real Time Clock:
0 to 23 hours
Min
Real Time Clock:
0 to 59 min
dAY
Real Time Clock:
Sun to Sat, day of the week
Hd1
First holiday of the week:
Sun to Sat
Hd2
Second holiday of the week:
Sun to Sat
iLE
Start time for silent mode on workdays:
(0.0 to 24h00min, res. 10 min) when the
silent mode is active the maximum speed of ventilators will be set to the value of
par.
FSS
.
dLE
Silent mode duration on workdays:
0.0 to 23h50min, res. 10 min
iSE
Start time for silent mode on holidays:
(0.0 to 24h00min, res. 10 min) when the
silent mode is active the maximum speed of ventilators will be set to the value of
par.
FSS
.
dSE
Silent mode duration on holidays:
0.0 to 23h50min, res. 10 min