Delay for temperature/pressure alarm activation on condenser:
0 to 255 min
HFC
Compressor stopped in case of any HAF alarm:
n; Y
HFL
Compressor capacity limitation in case of any HAF alarm:
0 to 80%, if
HFL=0
the compressor will be stopped.
dHF
Delay before stopping the compressor in case of any HAF alarm:
1 to 999 sec
PnF
Max number HAF alarms before stopping the regulation:
(0 to 15) after
detecting
PnF
alarms of the
HAF
type in an interval of time
PiF
, the regulation will
be stopped (if
HFC=Y
).
PiF
Interval of time to count the number of HAF alarms events:
0 to 999 min. With
PEi=0
this function is disabled.
FUP
Ventilators up time before maintenance:
(10 to 9990 hours, res. 10 hours) after
reaching the preset number of hours, the device will show the maintenance warning.
FPr
Number of ventilators active when probe FPb is in error:
0 to 2
15.11 DYNAMIC SETPOINT
dSP
Probe used for dynamic set point function:
nP; P1; P2; P3; P4
dSS
Dynamic setpoint value:
-
NTC10k
-40 to 110°C; -40 to 230°F
-
NTC86k
-40 to 180°C; -40 to 356°F
-
PT1000
-40 to 180°C; -40 to 356°F
dSb
Regulation band for dynamic setpoint:
-50 to 50°C; -90 to 90°F
dSd
Differential for dynamic SETPOINT:
-50 to 50°C; -90 to 90°F
15.12 ANALOGUE OUTPUT (OAN)
AoP
Analogue output reference probe (valid if oAn=PrP):
nP; P1; P2; P3; P4
LAo
Lower limit for analogue output:
input value (
AoP
) corresponding to the minimum
analogue output value (
Ao1
)
-
NTC10k
-40 to 110°C; -40 to 230°F
-
NTC86k
-40 to 180°C; -40 to 356°F
-
PT1000
-40 to 180°C; -40 to 356°F
-
0-5
0.0 to 51.0 bar; 0 to 750 PSI
UAo
Upper limit for analogue output:
input value (
AoP
) corresponding to the minimum
analogue output value (
Ao2
)
-
NTC10k
-40 to 110°C; -40 to 230°F
-
NTC86k
-40 to 180°C; -40 to 356°F
-
PT1000
-40 to 180°C; -40 to 356°F
-
0-5
0.0 to 51.0 bar; 0 to 750 PSI
Ao1
Minimum value for analogue output:
0 to 10Vdc
Ao2
Maximum value for analogue output: Ao1
to 10Vdc
Aot
Interval of time with analogue output at maximum time:
0 to 255sec
-
If
oAn=PrP
: after pasing
toA
value
-
If
oAn=EFn
: after start-up
SAo
Safety value for analogue output used in case of probe error (valid if
oAn=PrP):
0 to 100%
toA
Differential for analogue output:
0 to 100%
15.13 BUMP FUNCTION
bMP
BUMP function enabled:
n; Y
bon
Compressor ON time during BUMP function:
1 to 15 sec
boF
Compressor OFF time during BUMP function:
1 to 15 sec
nub
Number of cycles for BUMP function:
1 to 15