1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX
17/40
Alarm
Meaning
LPL
Low pressure alarm from external sensor (lockout)
11.2 ALARM MENU VISUALIZATION
1.
Press the alarm archive (
MEM
) button
2.
Scroll with
UP
or
DOWN
button up to label
AL0
(first alarm event memorized)
3.
Press
SET
button to enter the event submenu
4.
The encoding label relative to the logged event (par. 11.1) will be displayed
5.
Press
SET
button again to display the duration of the alarm event recorded
NOTE:
the visualization rules of the duration of any alarm event are the following:
a.
Resolution is 1 min for a duration from 0 to 900 min
b.
Resolution is 10 min for a duration from 15h00min to 99h.50min (on the
display: 15.0 to 99.5)
c.
Value of fixed to 99h.50min, with blinking decimal point, in the case of
exceeding this limit
6.
Press the
SET
button to move to the next alarm event
11.3 ALARM RESET
1.
Enter the ALARM menu
2.
To reset the alarm list, keep the SET button pressed for 5 sec until the message "CLr"
blinks on the display
3.
To reset the only event displayed, keep the ALR button pressed for 3 sec until the
message "rSA" blinks on the display
NOTE:
the current alarms will not reset
12. PARAMETER PROGRAMMING
12.1
“PR1” MENU
To access the parameter list Pr1 (user level), proceed as follows:
1.
Keep both
SET+DOWN
buttons pressed for 3 sec
2.
The display will show the name of the first parameter in the list
3.
Press the
SET
key to access to the stored value
4.
Change the value of the parameter using the
UP
and
DOWN
buttons
5.
Press the
SET
button to store the new value and move to the next parameter
EXIT:
press the
SET+UP
or wait for 30 seconds without pressing any key.
NOTE:
the new value will be stored even in case the exit from the programming menu is by
timeout.
12.2
“PR2” MENU
To access the Pr2 parameter list (protected level), proceed as follows:
1.
Enter the menu Pr1
2.
Keep both
SET+DOWN
buttons pressed for 7 sec
3.
The display will show the label "Pr2" (blinking)
EXIT:
press the
SET+UP
or wait for 30 sec without pressing any key.
NOTE:
each parameter in Pr2 level can be moved to the Pr1 level (user level) by pressing both