4 Chapter 1 Overview
RDU-S Rack Data Unit User Manual
Output parameters
Specification
Descriptions
Sensor power
output
12Vdc output
11.5Vdc ~ 12.5Vdc, maximum output
current: 0.8A
The output current is the total current which the
sensor power can provide. The total power
consumption of 12Vdc power does not exceed
10W
USB port output
Maximum output current: 500mA
-
1.2.3 Ambient Specifications
The ambient specifications of the data unit are listed in Table 1-6.
Table 1-6 Ambient specifications
Item
Requirement
Application location
Indoor
Working temperature*
0ºC ~ 45ºC
Relative humidity
5%RH ~ 95%RH (non-condensing)
Working environment
Dust: compliant with GR-63 indoor standard. No corrosive gas, flammable gas, oily mist, steam,
water drops or salt
Air pressure
70kPa ~ 106kPa
Storage temperature
-40ºC ~ +70ºC
Cooling
Natural cooling
Note*: It is the working temperature of the data unit, not including the sensors connected with it. Make sure that the used sensors
will not be damaged within the temperature range
1.2.4 Mechanical Specifications
The mechanical specifications of the data unit are listed in Table 1-7.
Table 1-7 Mechanical specifications
Dimensions (L × W × H)
Weight
440mm × 44.2mm × 55mm
≤
1.5kg
1.3 Options
The options of the data unit are listed in Table 1-8.
Table 1-8 Options
Classification
Optional model
Digital sensors
1. ER-ST01P infrared sensor (RJ45 port)
2. EE-SD01S smoke sensor (RJ45 port)
3. ER-DR02J door magnet sensor (RJ45 port)
4. EW-WT01B water sensor (RJ45 port)
5. IRM-S01W (5m, 10m) water sensor(RJ45 port)
6. SN-TH temperature & humidity sensor (RJ45 port)
7. SN-2D door dry contact sensor (RJ45 port)
8. SN-3C dry contact sensor (RJ45 port)
9. IRM-S01T intelligent temperature sensor (RJ45 port)
10. IRM-S02TH intelligent temperature/humidity sensor (RJ45 port)
11. SN-L leak detection sensor (RJ45 port)
Relay connectors
1. SL79LED stroboscopic alarm (two cables, non-RJ45 port)
2. HX-F8502 acousto-optic alarm (two cables, non-RJ45 port)
Cameras
1. KS-188 USB camera
2. ICAM-01 camera (with PTZ control)
Installation options of sensors
1. IDS-08 5cm simple installation support
2. Mushroom head magic paste
3. 16mm gummed magic paste
4. CT3Y 3cm round magnet
5. RJ45 three-way connector
Summary of Contents for RDU-S