Warning: These settings are factory set and should not be adjusted unless you have specific
instructions from the manufacturer.
METER CARD - SHORT CIRCUIT FAULT LEVEL MODE
This mode is used to adjust the short circuit alarm level. The alarm will be activated when the following
occurs
-
broken or damaged wire shorting to the cathode (steel)
-
anode not properly insulated from the cathode (steel) TO AJUST THE SHORT CIRCUIT FAULT LEVEL
-
Select the anode card to be adjusted by pressing the "SELECT' button on the face plate of the anode
card.
-
The green " SELECTED" LED will be illuminated.
-
Select the Short CCT fault level mode by pressing the " FAULT LEVEL (SHORT CCT) "button.
-
The word "LO" will appear on the first line of the LED readout.
-
Set the required voltage by pressing the " INCREASE" or "DECREASE' buttons on the anode card.
-
To De-select the card press the "DESELECT CARDS" button.