Warning: These settings are factory set and should not be adjusted unless you have specific
instructions from the manufacturer.
METER CARD - OPEN CIRCUIT FAULT LEVEL MODE
This mode is used to adjust the open circuit alarm level. The open circuit alarm will be activated when
the selected card's output voltage is higher than normal. This could be caused by:
-
broken anode wire
-
expired anode
-
disconnected anode
-
blown fuse on this anode card
-
fresh water or no water in anode locations
TO ADJUST THE OPEN CIRCUIT FAULT LEVEL
-
Select the anode card to be adjusted by pressing the "SELECT" button on the faceplate of the anode
card.
-
The green "SELECTED" LED will be illuminated.
-
Select the Open CCT fault level mode by pressing the " FAULT LEVEL (OPEN CCT)" button.
-
The word "Hf' will appear on the first line of the LED readout.
-
Set the required voltage by pressing the "INCREASE" or "DECREASE" buttons on the - anode card.
-
To De-select the card press the "DESELECT CARDS" button Refer to Figure #3 on the next page.