5
Configuring Priority and Non-Priority Load Circuits
CAUTION:
Power must be OFF during configuration! Only one screw may be
removed.
1.
Remove the F1, F2… plastic cover
by
unscrewing the cover’s frontal screw,
then inserting a small screwdriver into the cover’s gap and
carefully press down and out to release the locking tabs.
2.
Switch OFF and unplug the actual MCBs
by
switching the MCB handle to “0” (upwards),
then using your fingers to pull out the MCB
3.
Remove the actual Priority Load Screw
by
using a screwdriver to unscrew the Priority Load Screw
(refer to table below).
Keep the removed screw in the clip, on the cover’s inside
Details
Installation
Plug for MCB1
MCB1
MCB8
Minipack
front
0
1
MCB8
(Upper and
lower plugs)
Removing or Mounting Load MCBs
CAUTION:
Power must be OFF during this operation!
1.
Remove the F1, F2… plastic cover
by
unscrewing the cover’s frontal screw,
then inserting a small screwdriver into the cover’s gap and
carefully press down and out to release the locking tabs.
2.
Switch OFF the MCB
by
switching the MCB handle to “0” position (upwards)
3.
Remove or insert the MCB
by
using your fingers — or the MCB extraction tool, if
available — to pull out and unplug the MCB
or
pressing the MCB into the upper and lower plugs
Screw Removed
F1
F2
F3
F4
F5
F6
F7
F8
F9 F10
None
P
P
P
P
P
P
P
P
P
P
Y25
NP
NP
NP NP
NP
NP
NP
NP
P
P
Y24
NP
NP
NP NP
NP
NP
P
P
P
P
Y7
NP
NP
NP NP
P
P
P
P
P
P
Y6
NP
NP
P
P
P
P
P
P
P
P
WARNING: Only one screw can be removed at a time.
P
=Priority Load Circuits
NP =Non Priority Load Circuits
Configuration of Priority & Non Priority Load Circuits
Plugs for MCB1
Priority Load Screws
(accessible with unplugged MCBs)
F3-F10 Screw (Y6)
F5-F10 Screw (Y7)
F7-F10 Screw (Y24)
F9-F10 Screw (Y25)