Load Monitor CAN Node
The
Load Monitor CAN Bus Node
enables you to decentralize and increase the number of input
fuse monitoring and current sense signals in your
Smartpack
based DC power supply system. The
fuse monitoring inputs are suitable for monitoring a wide range of breakers in both positive and
negative DC distributions.
Read also the “Installation Guide
Load Monitor CAN Node”,
document 351506.033.
CAN Bus Nodes
Appendix
CAN port 1&2
Electrically identical
DIP switches
CAN ID address
DIP switch #1
Load Monitor
Power
LED Lamp (green)
Warning
LED Lamp (yellow)
Alarm
LED Lamp (red)
Fuse Monitoring Inputs
Terminal Block X*
Input 1
Load Monitor
DIN Rail
mounting
clips
Screw head
mounting slot (2x)
(Head’s diameter >5 mm
and <8 mm)
Current Sense Inputs
Terminal Block X**
Input 1
Load Monitor Connections
Voltage free relay outputs and Configurable monitoring inputs
FUNCTION
SIGNAL PIN-OUT
Load Monitor
To next
CAN bus node
CAN
port 1&2
RJ45, 8 pins
From p
revious
CAN bus node
O
r
R
J45 C
A
N
b
u
s t
e
rm
ina
tion pl
ug, i
f th
e L
oad
M
oni
tor
is
th
e l
a
st
no
de
in
the C
A
N
bus
(Customer Connections)
1.5 mm
2
, max.
wire section
DIP
Switches
(5-8 always
OFF)
1
2
3
4
Input Circuit 1
Input Circuit 2
Input Circuit 3
Input Circuit 4
6
Config. Input
(F
ro
m
br
eaker
s a
n
d
ex
ter
n
al
equi
pm
ent)
3
2
1
4
5
Config. Input
Config. Input
Config. Input
Config. Input
Config. Input
Input Circuit 5
Input Circuit 6
Fuse M
oni
torin
g
Inp
u
ts
+
–
+
–
–
–
+
–
+
+
+
–
X:*
+
–
+
–
8
Config. Input
7
Config. Input
Input Circuit 7
Input Circuit 8
Input Circuit 1
Input Circuit 2
Input Circuit 3
Input Circuit 4
6
Sense Input
(Fro
m cu
rre
n
t sh
un
ts
)
3
2
1
4
5
Sense Input
Sense Input
Sense Input
Sense Input
Sense Input
Input Circuit 5
Input Circuit 6
Current
Sense I
npu
ts
+
–
+
–
–
–
+
–
+
+
+
–
X:**
+
–
+
–
8
Sense Input
7
Sense Input
Input Circuit 7
Input Circuit 8
Load
Monitor
ID
#
DIP Switch Position
1
⎯
2
⎯
3
⎯
4
1
st
Monitor
49
OFF
⎯
OFF
⎯
OFF
⎯
OFF
2
nd
Monitor
50
ON
⎯
OFF
⎯
OFF
⎯
OFF
3
rd
Monitor
51
OFF
⎯
ON
⎯
OFF
⎯
OFF
4
th
Monitor
52
ON
⎯
ON
⎯
OFF
⎯
OFF
5
th
Monitor
53
OFF
⎯
OFF
⎯
ON
⎯
OFF
6th Monitor
54
ON
⎯
OFF
⎯
ON
⎯
OFF
7
th
Monitor
55
OFF
⎯
ON
⎯
ON
⎯
OFF
8
th
Monitor
56
ON
⎯
ON
⎯
ON
⎯
OFF
9
th
Monitor
57
OFF
⎯
OFF
⎯
OFF
⎯
ON
10
th
Monitor
58
ON
⎯
OFF
⎯
OFF
⎯
ON
11
th
Monitor
59
OFF
⎯
ON
⎯
OFF
⎯
ON
12
th
Monitor
60
ON
⎯
ON
⎯
OFF
⎯
ON
13
th
Monitor
61
OFF
⎯
OFF
⎯
ON
⎯
ON
14
th
Monitor
62
ON
⎯
OFF
⎯
ON
⎯
ON
Load Monitor
DIP switch configuration
ID <49>
(All switches OFF)
Note:
•
DIP switch
positions 5
through 8 are
always to be OFF
•
The monitor’s
ID # corresponds
to the DIP
switch’s binary
value plus 49