Quick Start Guide
Minipack PS System
356808.103, 1v2-2008-10
15
External AC Fuses
⎯
Recommended Rating
The site’s AC supply quality is of great importance. In general, a site with better AC supply quality
(stable nominal voltage) may use smaller breakers.
CAREFUL:
Minipack systems using 48V-400W rectifiers may also use the recommended external breakers specified in the 800W
Rectifiers table above, even though smaller breakers could be employed.
For more information, read document 2028364
WARNING:
Always replace a rectifier with blown internal AC fuse with a new module, and send the malfunctioning module for servicing.
WARNING:
You must always consider re-dimensioning the external AC fuses and AC cabling, before swapping 400W, 800W or
800W WIR Minipack rectifiers in the same Minipack system.
AC Mains
Appendix
AC Mains
No of
Current Max.
Ext. Fuse
Input Type
Rectifiers
per input (A)
205VAC
185VAC
Type
205VAC
185VAC
N
3 phase (Y)
I
4
8.77
{ 9.72} 10A-D/16A-C {
←
equal}
II
6
(equal row I)
(equal row I)
230VAC
3 phase (
Δ
)
III
4
15.2
{ 16.8}
16A-C
{20A-C}
IV
6
(equal row III)
(equal row III)
230VAC
1 phase
V
4
17.5
{ 19.4}
20A-C
{
←
equal}
VI
6
26.3
{ 29.5}
32A-C
{
←
equal}
Doc 2024398,1v0
Notes:
•
Use the values in {} brackets in the 185VAC column, if you are
unsure or know that the available AC mains voltage may drop
below 205VAC.
•
Each phase feeds two 800W rectifiers
•
The recommendations apply for use of Thermal magnetic circuit
breaker, type Siemens 5SX or 5SY series, MG C60H series or
similar. For more information regarding External AC fuses and
other types of fuses, please read the document 2024398.
Recommended External AC Fuses per AC Mains Feed Input
Minipack Systems with 48 VDC 800W Rectifiers
AC Mains
No of
Current Max.
Ext. Fuse
Input Type
Rectifier
s
per input (A)
230VAC
150VAC
100VAC
Type
230VAC
150VAC 100VAC
N
3 phase (Y)
I 4
7.73
{ 7.73}
[14.22]
25A-C {
←
equal} [
←
equal]
II 6
(equal row I)
(equal row I)
230VAC
3 phase (
Δ
)
III 4
(equal row I)
(equal row I)
IV 6
(equal row I)
(equal row I)
230VAC
1 phase
V 2
7.73
{ 11.9}
[14.3]
(equal row I)
VI 4
15.5
{ 23.7}
[28.5]
25A-C {32A-C}
[32A-C]
VII 6
23.2
{ 35.6}
[42.7]
32A-C {40A-C} [50A-C]
Doc 2043538,1v0
Notes:
•
Use the values in {} brackets in the 150VAC column, if you are unsure or know that the
available AC mains voltage may drop between 230VAC and 150VAC, or use the
values in [] brackets in the 100VAC column if the voltage may drop below 150VAC.
•
Each phase feeds two 800W WIR rectifiers (Wide Input Range)
•
The recommendations apply for following air breaker types:
- Up to 32A, use Melnrining DBN32 C char series or similar
- Bigger than 32A, use Melnrining DB47-63A C char series or similar.
For more information regarding External AC fuses and other types of fuses, please
read the document 2043538.
Recommended External AC Fuses per AC Mains Feed Input
Minipack Systems with 48 VDC 800W WIR Rectifiers