Data Logger DL210
Elster-Instromet GmbH
85
Bd.S1 Baud rate for optical head / direct readout cable
Setting for the baud rate of the 1
st
serial interface. Practical values are located in
the range from 1200 to 9600 baud.
CW1.S Call window 1, start
(e.g. 01,07:30)
CW1.E Call window 1, end
(e.g. 01,09:30)
CW2.S Call window 2, start
(e.g. 01,12:00)
CW2.E Call window 2, end
(e.g. 01,13:00)
CW3.S Call window 3, start
(e.g. 00:00)
CW3.E Call window 3, end
(e.g. 23:59)
CW4.S Call window 4, start
(e.g. 01,00:00)
CW4.E Call window 4, end
(e.g. 01,00:00)
Data recalls via the modem are only possible at the times defined by these time
windows. In contrast the sending of SMS messages occurs independently of the
call windows.
The call windows 1 and 2 are conceived in order to be able to only establish a
connection to the DL210 at certain times during
battery operation
. Outside of these
windows a connection is only established with an external voltage supply and an
appropriately configured time window 3 or 4.
The call windows 1 and 2 should be as short as possible so that the modem
battery is not loaded unnecessarily. For more details on calculating the service life
see Chapter: 3.6.3.
The call windows 3 and 4 are conceived in order to be able to only establish a
connection at certain times during
external voltage supply
. Outside of these
windows or when the voltage supply fails, a connection is established in the
battery mode with an appropriately configured time window 1 or 2. With an
external mains supply it is practicable to configure one of these time windows to
"daily, 00:00 hrs – 23:59 hrs"!
Using the WinPADS parameterisation software the time window periods can be
set to monthly, weekly or daily.
With the above example values for the call window incoming calls are accepted
with an external voltage supply present daily between 00:00 hrs and 23:59 hrs. If
the external voltage supply fails, then with a modem battery present a call is only
accepted on the 1
st
of the month between 07:30 hrs and 09:30 hrs, as well as
between 12:00 hrs and 13:00 hrs.
CWTst "Test" call window
The "Test" call window enables the GSM modem to be switched on for a
parameterised time (e.g. 30 minutes) to make, for example, test calls. The
smallest possible entry is two minutes. After initiating the function the display is
refreshed every minute and indicates the remaining open time of the call window.
This call window is also opened for two minutes if the GSM parameters in the
display are to be updated and in this period no call window (1 – 4, see above) is
open.
RES.1 Last response to Message 1
Result of the last message which was sent to Phone Number 1.
RES.2 Last response to Message 2
Result of the last message which was sent to Phone Number 2.
Summary of Contents for DL210
Page 2: ...Data Logger DL210 2 Elster Instromet GmbH ...
Page 9: ...Data Logger DL210 Elster Instromet GmbH 9 ...
Page 10: ...Data Logger DL210 10 Elster Instromet GmbH ...
Page 11: ...Data Logger DL210 Elster Instromet GmbH 11 Part 1 Device description relevant to calibration ...
Page 101: ...Data Logger DL210 Elster Instromet GmbH 101 Part 2 Description of the Initial operation ...
Page 118: ...Data Logger DL210 118 Elster Instromet GmbH Appendix ...