Data Logger DL210
Elster-Instromet GmbH
39
MdMI1 Mode for monitoring Input 1
MdMI2 Mode for monitoring Input 2
Various modes for monitoring can be programmed. The following modes are
possible:
Mode for monitoring
Explanation
1
0
Switched off
No monitoring
1
> L.MI1
Limit exceeded (value > L.MI1)
2
³
L.MI1
Limit exceeded (value
³
L.MI1)
3
< L.MI1
Limit undercut (value < L.MI1)
4
£
L.MI1
Limit undercut (value
£
L.MI1)
5
Time-synchronous input Time-synchronous input, rising edge
Depending on the system other values can be set (6, 9, 10, 12, 13, 17, 21, 23 and
33). However, here they cannot be used practicably and should therefore not be
set.
SC.I1 Source for monitoring Input 1
SC.I2 Source for monitoring Input 2
With activated monitoring and in dependence of the programmed mode (MdMI1
or MdMI2), a source must also be defined, with the contents of which the limit is
compared (i.e. the value that is to be monitored).
The address of the value to be monitored must be set as a source. The following
sources are practicable in dependence of the set mode (extract only):
Mode for monitoring
Source for monitoring
0
Switched off
No monitoring.
1
> L.MI1
2
³
L.MI1
3
< L.MI1
4
£
L.MI1
1:160 (V1MP, measuring period counter)
2:160 (V1Dy, day counter)
1:210 (Q1, flow)
1:228 (St.I1, input status, Input 1)
5
Time-synchronised input 1:228 (St.I1, input status, Input 1)
CP.I1 cp value signal input I1
The cp value states the pulse weighting as pulses per unit, pulses/m³. The value is
displayed with eight places without leading zeroes in which 5 predecimal and 3
post-decimal places are used.
The cp value of the input does not influence the format of the counter readings.
They are always displayed with nine predecimal and four post-decimal places.
SNM Serial number of the meter (4 + 8 places)
Here the 12-figure serial number of the meter connected to this signal input is
displayed. Ex-works 000000000002 is the default.
1
The "value" quoted here can be freely set with "SC.I1" or "SC.I2".
Summary of Contents for DL210
Page 2: ...Data Logger DL210 2 Elster Instromet GmbH ...
Page 9: ...Data Logger DL210 Elster Instromet GmbH 9 ...
Page 10: ...Data Logger DL210 10 Elster Instromet GmbH ...
Page 11: ...Data Logger DL210 Elster Instromet GmbH 11 Part 1 Device description relevant to calibration ...
Page 101: ...Data Logger DL210 Elster Instromet GmbH 101 Part 2 Description of the Initial operation ...
Page 118: ...Data Logger DL210 118 Elster Instromet GmbH Appendix ...