06/2022
| 56 |
924EHUCE4.00 - Mistral
Humidifier
Par. Description
MU
Range
PW
Default
TEMPERATURE ALERTS group
A5 Low humidity alert threshold only if CFG
=2,3,4,7,8,9.Fixedhysteresis=2%.
---
0...100
M
20
A6 High humidity alert threshold only if CFG
=2,3,4,7,8,9.Fixedhysteresis=2%.
---
0...100
M
95
A7 High low humidity alert delay only if CFG
=2,3,4,7,8,9
.
s
0...999
M
120
A13
Number of fan operating hours to signal partial operating hours.
The count can be reset to zero by pressing and holding for at least 4 s.
1000h
0...99
M
60
DIGITAL INPUTS group
i0
ID2 port digital input polarity.
0 = Normally closed; 1 = Normally open.
---
0/1
M
0
PASSWORD group
PAS Parameter access password.
num
-99...999
M
-19
EVLINK DATALOGGING group
bLE
Serial port configuration for EVconnect/EPoCA connectivity.
0 = Spare;
1
=ForcedforEVconnectorEPoCA;
2...99
=EPoCAlocalnetworkaddress.
---
0...99
M
1
rE0 Datalogger sampling interval
min
0...240
M
60
rE1
Enable data logging for data logger.
0 = No;
1 = Yes.
Logged data:
•
Humiditysensor(iffitted);
• Temperature sensor (level board);
•
Mist-makeroutputstatus;
•
Fanoutputstatus;
• EEVC output status;
• EEVS output status.
---
0/1
M
0
MODBUS SERIAL CONFIGURATION group
LA1 COM1 serial line modbus protocol controller address.
num
1...247
M
20
LA1 COM2 serial line modbus protocol controller address.
num
1...247
M
247