29
Parameter setting
Sensors Mini-Sewi KNX TH-L-Pr and Mini-Sewi KNX L-Pr
• Version: 30.08.2018 • Technical changes and errors excepted.
The light regulation can be
interrupted during switching or dimming
by response
objects, i.e. nothing else is transmitted via the dim-output. This results in the manual
light operation having priority.
Set, which objects will trigger interruption and when the regulation is to be continued.
Note: If the criteria for the continuation of the regulation are fulfilled, the regulation,
however, has just been stopped by an object or is blocked, then the end of the inter-
ruption has no effect on the behaviour of the light.
The light regulation can be
blocked
via the bus. In contrast to the interruption, when
blocking, a switching command or brightness value can be sent. Upon release, the out-
put behaviour follows the rule.
Target / actual difference in Lux
(for a deviation in Lux)
1...2500; 100
Dimmer increments
100.00% • 50.00% • 25.00% • 12.5% • 6.25% •
3.13% • 1.56%
Repetition of the dim command in seconds
1...600; 6
Dim brighter with response value in %
1...100
Dim darker with response value in %
0...99
Use interruptions
No •
Yes
Interrupt regulation when
Reception from response switching object
No • Yes
Reception from response dimming object
No • Yes
Continue regulation
• after a waiting period
• at movement after waiting period
• at object reception after waiting period
• at object reception or after waiting period
• at movement after object reception
• at object reception or movement after
waiting period
Waiting period in seconds
5...72000
(Standard value depending on the
setting of "continue regulation")
Object value
0 • 1 • 0 or 1
Use block
No •
Yes
Analysis of the blocking object
• at value 1: block | at value 0: release
• at value 0: block | at value 1: release
Value prior to initial communication
0 • 1
Output pattern
On block
• send nothing
• send off command
• send on command
• send value