background image

Power Supply Systems KNX PS640(USB) 



 Version: 155.05.2013 



 Subject to technical changes. Errors excepted. 

2

The Power Supply Systems KNX PS640 and KNX PS640 USB deliver a 29 V bus voltage 
for the KNX system and 24 V DC supply voltage for 24 V devices. Special operating 
conditions such as short circuit, overvoltage, overload or excess temperature are 
recorded and may be read off on the display. The present power discharge is displayed 
as well. It is possible to reset the connected bus devices directly by means of the key 
pad. 
 

Functions:  

·

 

Delivers a 

29 V KNX bus voltage

 (reduced), output current max. 640 mA, short-

circuit proof  

·

 

Delivers 

24 V DC

 (not reduced), output current max. 150 mA  

·

 

Reset

 of a line directly on the device  

·

 

Record of operating hours, overload, external overvoltage, internal overvoltage, 
short circuit and excess temperature 

·

 

Display of operating data bus voltage, bus current and temperature of the device 

·

 

The display may be shown in German, English, Spanish or Dutch  

·

 

Only 

KNX PS640 USB

: USB interface for bus access via PC 

 

Technical data 

Housing 

Plastic material 

Colour 

White 

Mounting 

Snap-on fitting on mounting rails 

Protection category 

IP 20 

Dimensions 

approx. 123 x 89 x 61 (W x H x D, mm), 7 width units 

Weight 

approx. 370 g 

Ambient temperature 

Operation -5…+45 °C, storage -25…+70°C 

Ambient air humidity 

max. 95% RH, avoid bedewing 

Operating voltage 

230 V AC , 50 Hz 

Power consumption Standby 

approx. 2.3 W 

Outputs 

 KNX bus voltage 29 V (reduced),  

  Output current max. 640 mA, short-circuit proof  

 24 V DC (not reduced), Output current max. 150 mA 

 
The following standards have been considered for the evaluation of the product in 
terms of electro magnetic compatibility: 
Transient emissions:  

·

 

EN 60730-1:2000 Section EMV (23, 26, H23, H26) (threshold category: B) 

·

 

EN 50090-2-2:1996-11 + A1:2002-01 (threshold category: B) 

·

 

EN 61000-6-3:2001 (threshold category: B) 

Interference resistance: 

·

 

EN 60730-1:2000 Section EMV (23, 26, H23, H26) 

·

 

EN 50090-2-2:1996-11 + A1:2002-01 

Summary of Contents for KNX PS640

Page 1: ...640 USB Technical Data and Installation Notes Elsner Elektronik GmbH Steuerungs und Automatisierungstechnik Herdweg 7 D 75391 Gechingen Germany Phone 49 0 70 56 93 97 0 Fax 49 0 70 56 93 97 20 info elsner elektronik de www elsner elektronik de ...

Page 2: ...tage bus current and temperature of the device The display may be shown in German English Spanish or Dutch Only KNX PS640 USB USB interface for bus access via PC Technical data Housing Plastic material Colour White Mounting Snap on fitting on mounting rails Protection category IP 20 Dimensions approx 123 x 89 x 61 W x H x D mm 7 width units Weight approx 370 g Ambient temperature Operation 5 45 C ...

Page 3: ...tions for use any warranty or guarantee claim will be void After unpacking the device check immediately for any mechanical damages In case of transport damage this must immediately notified to the supplier If damaged the power supply system must not be put into operation If an operation without risk may supposedly not be guaranteed the plant must be put out of operation and be secured against acci...

Page 4: ... Housing 1 Bus KNX terminal 2 Bus KNX terminal 3 Input operating voltage 230 V AC L N PE 4 USB interface only KNX PS640 USB 5 Output direct current voltage 24 V DC Connections 3 and 5 are suitable for solid conductors up to 1 5 mm or conductors with fine wires Scheme Auxiliary supply 24 V DC max 150 mA ...

Page 5: ...ay is dimmed after 60 seconds if during this period no key is pressed Line reset Standard screen Press key once Press key once more in order to get into the sector Line reset Move the cursor flashing rectangle at right edge to the desired setting with the keys or and confirm with key Yes Reset is activated The line is switched to neutral and shorted The basic setting displays Reset is active No Re...

Page 6: ... and confirm with key Move the cursor to the desired menu with the up and down keys and press key Operating hours The operating hours of the power supply system are displayed in years days and hours With key you return to the previous menu level Overload The number of overload incidents and the total time in days hours and minutes are displayed With key you return to the previous menu level elsner...

Page 7: ... Excess Temperature The number of excess temperature incidents on the circuit board of the device is displayed With key you return to the previous menu level Operating data Standard screen Press key once Move the cursor flashing rectangle at right edge to the Operating Data menu with the keys and and confirm with key elsner elektronik KNX Power Supply Normal Operation Diagnostics Bus Voltage 29 4 ...

Page 8: ...the cursor flashing rectangle at right edge to the Language menu with the keys and and confirm with the key Move the cursor to the desired language with the up and down keys and press the key The display automatically jumps to the previous menu in the desired language With key you get back by one menu level to the basic setting elsner elektronik KNX Power Supply Normal Operation Diagnostics Sprach...