Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200545_03B May 2016                        ©2016 ELMDENE INTERNATIONAL LTD  

 

S

IGNALLING 

O

UTPUTS

 

 

 
Rating: 

0.10A @ 60Vdc 16Ω solid state relay contacts, volt free. 

EPS Fault:  

Open if Loss of mains for >8s 

GEN Fault: 

Open if Battery terminal voltage < 11.5v (when operating in standby with no 
mains present), battery not present or Output and/or battery fuse blown 

Tamper:  

0.5A @ 30Vdc volt free contact. Open when lid is open.  

 

C

ONNECTIONS

   

 
O/P +, - 

Connection to equipment to be powered (Observe polarity) 

 

EPS Fault: 

Relay output for mains fail. Open if loss of mains. 

GEN Fault: 

Relay output for General Fault. Open in fault condition 

BATT +, - 

Connection to standby battery. Use cables provided (Observe polarity) 

 

I

NSTALLATION AND 

C

OMMISSIONING

 

 

 

 

This unit is only suitable for installation as permanently connected equipment.  This PSU is

 

NOT SUITABLE 

for 

external installation. 

 EQUIPMENT MUST BE EARTHED

. Before installation, ensure that external disconnect 

device is

 OFF

.

 

The PSU should be installed according to all relevant safety regulations applicable to the 

application.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

Fig 1  Mounting of Power Supply 

L E N

 

Min 10cm clearance

 

Fasten cables 
using cable tie

 

 

 

3A min

 

FUSED 
SPUR  

Load output cable: 
Current rating to 
match maximum load

 

Mains Input cable rated: 
3A, 300Vac minimum

 

Summary of Contents for GEN2-08 Series

Page 1: ...a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging and a fault condition Comprehensive protection is built in as standar...

Page 2: ...x 200 x 80 355 x 330 x 80 330x 275 x 80 Weight kg excluding battery 2 0 4 0 3 3 Material 1 2mm steel white powder coated Environmental Temperature 10 to 40 C operating 75 RH non condensing 20 to 80 C...

Page 3: ...mains fail Open if loss of mains GEN Fault Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity INSTALLATION AND COMMISSIONING...

Page 4: ...rectly rated load cable through supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green Mains LED is ON NOTE...

Page 5: ...ntinue to supply voltage and current to the output load Check that Green Mains LED is OFF and the control panel displays a Loss of Mains EPS fault NOTE Batteries must have sufficient charge to supply...

Page 6: ...er retaining feature engaging over the bottom lip of the base fasten with screws supplied 21 Check that the tamper switch is CLOSED when the lid cover is closed and the retaining screws are fitted OPE...

Page 7: ...E parts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentati...

Page 8: ...WEEE and 2013 56 EU Battery At the end of life the product must be separated from the domestic waste stream and disposed via an appropriate approved WEEE disposal route in accordance with all national...

Reviews: