3
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200545_03B May 2016 ©2016 ELMDENE INTERNATIONAL LTD
S
IGNALLING
O
UTPUTS
Rating:
0.10A @ 60Vdc 16Ω solid state relay contacts, volt free.
EPS Fault:
Open if Loss of mains for >8s
GEN Fault:
Open if Battery terminal voltage < 11.5v (when operating in standby with no
mains present), battery not present or Output and/or battery fuse blown
Tamper:
0.5A @ 30Vdc volt free contact. Open when lid is open.
C
ONNECTIONS
O/P +, -
Connection to equipment to be powered (Observe polarity)
EPS Fault:
Relay output for mains fail. Open if loss of mains.
GEN Fault:
Relay output for General Fault. Open in fault condition
BATT +, -
Connection to standby battery. Use cables provided (Observe polarity)
I
NSTALLATION AND
C
OMMISSIONING
This unit is only suitable for installation as permanently connected equipment. This PSU is
NOT SUITABLE
for
external installation.
EQUIPMENT MUST BE EARTHED
. Before installation, ensure that external disconnect
device is
OFF
.
The PSU should be installed according to all relevant safety regulations applicable to the
application.
Fig 1 Mounting of Power Supply
L E N
Min 10cm clearance
Fasten cables
using cable tie
3A min
FUSED
SPUR
Load output cable:
Current rating to
match maximum load
Mains Input cable rated:
3A, 300Vac minimum