2
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200545_03B May 2016 ©2016 ELMDENE INTERNATIONAL LTD
S
PECIFICATION
Mains Input
Rated Voltage / (Operational Voltage)
100-240Vac / (90 – 265Vac)
Frequency
50/60Hz
Input current
GEN2-08
&
GEN2-18 < 1.0A
at full load
Fuse
T2A 20mm HRC
Output
GEN2-08-y
GEN2-18-y
Voltage at full load
Mains power
Battery standby
12.8 –14.2Vdc (13.8Vdc nominal)
9.8 – 13.0Vdc
Ripple
<400mV pk – pk max @ Rated Voltage
Fuse
Load
Battery
F1.0A
F1.0A
F1.6A
F1.6A
Continuous Output Current
*
Mains
Battery for 12 hours
1.0 A
0.6A with 8Ah Battery
1.5A
1.5A with 18Ah Battery
*See below for quiescent current of PSU under battery when calculating total system standby current resources.
Mechanical
Product Reference
GEN2-08-A
GEN2-08-B
GEN2-18-B
GEN2-08-C
GEN2-18-C
Enclosure Dimensions
w x h x d (mm)
230 x 200 x 80
355 x 330 x 80
330x 275 x 80
Weight (kg)
excluding battery
2.0
4.0
3.3
Material
1.2mm steel white powder coated
Environmental
Temperature
-10 to +40°C (operating) 75% RH non-condensing
-20 to +80°C (storage)
Standby Battery Management
Warning: risk of explosion if incorrect battery type fitted
Maximum Battery Size
GEN2-08: 8Ah 12V Valve Regulated Lead Acid
(Not supplied with unit)
GEN2-18: 18Ah 12V Valve Regulated Lead Acid
Intelligent Battery Recharge Time:
< 72 hours to 80% - A heavily discharged battery having a
terminal voltage > 9.0V will attempt to be charged.
Testing:
Battery Not Present: <9.0V battery voltage
Low battery voltage: <11.5V (no mains present)
Protection:
Reverse battery connection protection
Deep discharge protection - Battery disconnect at 10.6V battery
terminal voltage
Quiescent Current:
64 mA when running on battery - less than 1 mA after deep
discharge protection.
Battery Cold Start (BCS)
Momentarily link BCS pins together to connect battery to load if
PSU commissioned without any mains