Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200545_03B May 2016                        ©2016 ELMDENE INTERNATIONAL LTD  

 

S

PECIFICATION

 

 

 

Mains Input 

Rated Voltage / (Operational Voltage) 

100-240Vac / (90 – 265Vac) 

Frequency  

50/60Hz 

Input current 

GEN2-08 

GEN2-18 < 1.0A 

at full load 

Fuse 

T2A 20mm HRC 

 

Output 

 

GEN2-08-y 

GEN2-18-y 

Voltage at full load 

 

Mains power 

 

Battery standby 

 
 

12.8 –14.2Vdc (13.8Vdc nominal) 

 

9.8 – 13.0Vdc  

Ripple 

<400mV pk – pk max @ Rated Voltage 

 

Fuse 
 

Load 

 

Battery 

 

F1.0A 
F1.0A 

 

F1.6A 
F1.6A 

Continuous Output Current

*

 

 

Mains  

 

Battery for 12 hours 

 

1.0 A 

0.6A with 8Ah Battery 

 

1.5A 

1.5A with 18Ah Battery 

*See below for quiescent current of PSU under battery when calculating total system standby current resources. 

 

Mechanical 

Product Reference 

GEN2-08-A 

GEN2-08-B

 

GEN2-18-B 

GEN2-08-C

 

GEN2-18-C 

Enclosure Dimensions

 w x h x d (mm) 

230 x 200 x 80 

355 x 330 x 80 

330x 275 x 80 

Weight (kg)

 excluding battery 

2.0 

4.0 

3.3 

Material  

1.2mm steel white powder coated 

 

Environmental  

Temperature  

 -10 to +40°C (operating) 75% RH non-condensing  

 

 -20 to +80°C (storage) 

 

Standby Battery Management              

Warning: risk of explosion if incorrect battery type fitted 

 

Maximum Battery Size 

GEN2-08:  8Ah 12V Valve Regulated Lead Acid 

(Not supplied with unit) 

GEN2-18:  18Ah 12V Valve Regulated Lead Acid 

 

Intelligent Battery Recharge Time:  

< 72 hours to 80%  -  A heavily discharged battery having a 
terminal voltage > 9.0V will attempt to be charged. 

 

Testing: 

Battery Not Present: <9.0V battery voltage 

 

Low battery voltage: <11.5V (no mains present) 

 

 

Protection: 

Reverse battery connection protection 
Deep discharge protection - Battery disconnect at 10.6V battery 
terminal voltage 

 

Quiescent Current: 

64 mA when running on battery - less than 1 mA after deep 
discharge protection. 

 

Battery Cold Start (BCS) 

Momentarily link BCS pins together to connect battery to load if 
PSU commissioned without any mains 

Summary of Contents for GEN2-08 Series

Page 1: ...a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging and a fault condition Comprehensive protection is built in as standar...

Page 2: ...x 200 x 80 355 x 330 x 80 330x 275 x 80 Weight kg excluding battery 2 0 4 0 3 3 Material 1 2mm steel white powder coated Environmental Temperature 10 to 40 C operating 75 RH non condensing 20 to 80 C...

Page 3: ...mains fail Open if loss of mains GEN Fault Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity INSTALLATION AND COMMISSIONING...

Page 4: ...rectly rated load cable through supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green Mains LED is ON NOTE...

Page 5: ...ntinue to supply voltage and current to the output load Check that Green Mains LED is OFF and the control panel displays a Loss of Mains EPS fault NOTE Batteries must have sufficient charge to supply...

Page 6: ...er retaining feature engaging over the bottom lip of the base fasten with screws supplied 21 Check that the tamper switch is CLOSED when the lid cover is closed and the retaining screws are fitted OPE...

Page 7: ...E parts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentati...

Page 8: ...WEEE and 2013 56 EU Battery At the end of life the product must be separated from the domestic waste stream and disposed via an appropriate approved WEEE disposal route in accordance with all national...