36
FAP54 Installation
Code
Error
42
Update loop mode initialization: lack of 4 consecutive addresses to assign to a multiple I/O
module.
43
Update loop mode initialization: missing answer in current from the point or open circuit.
The procedure completes correctly when a voltage on LB is detected.
46
Update loop mode initialization: missing answer from a point with valid (1 – 128) address.
The module could not communicate with the point: check the electrical connections.
47
Update loop mode initialization: line fault (overload / short circuit) after point addressing or
acquisition.
Check the electrical connections after the just addressed/acquired point.
48
Update loop mode initialization: maximum number of points reached and lack of voltage on LB.
The procedure completes correctly when a voltage is found on LB; warning: do not overcome
the limit of max 128 points per line.
49
Update loop mode initialization: the maximum number of addressed points has been reached
and there are other points not addressed yet on the line.
Warning: do not overcome the limit of max 128 points per line.
50
Update loop mode initialization: reached the maximum number of generated random
addresses.
Repeat the procedure and/or manually address the points not yet addressed.
60
Auto-addressed open mode initialization: line fault (overload or shortcircuit) at power on.
Check the electrical connections among the circuit module and the points connected directly
with LA and LB.
61
Auto-addressed open mode initialization: unexpected voltage on line LB.
A voltage on LB terminals has been detected at the beginning of the initialization procedure;
this voltage is probably due to an unwanted connection between line LA and line LB.
62
Auto-addressed open mode initialization: lack of 4 consecutive addresses to assign to a
multiple I/O module.
65
Auto-addressed open mode initialization: missing answer from a point with invalid address.
The module could not communicate with the point: check the electrical connections.
66
Auto-addressed open mode initialization: no answer from a point with valid (1-128) address.
The module could not communicate with the point: check the electrical connections.
67
Auto-addressed open mode initialization: Missing answer from a point with valid (1–128)
address.
The module could not communicate with the point: check the electrical connections.
70
Auto-addressed open mode initialization: unexpected voltage is found on LB while the
procedure is in progress on line LA.
Check that the detection line connected to LA is not connected to LB.
71
Auto-addressed open mode initialization: no answer from the point during the address
assignment phase.
Check the electrical connections after the point.
72
Auto-addressed open mode initialization: point with random address not found.
Check the electrical connections.
80
Pre-configured open mode initialization: line fault (overload or shortcircuit) at power on.
Check the electrical connections among the circuit line card and the points connected directly
with LA and LB.
87
Pre-configured open mode initialization: line fault (overload / short circuit) after point addressing
or acquisition.
Check the electrical connections after the just addressed/acquired point.
88
Pre-configured open mode initialization: maximum number of points reached.
Warning: do not overcome the limit of max 128 points per line.
89
Pre-configured open mode initialization: there is a point with invalid address.
The procedure only works with points having valid addresses (range 1 – 128).
100
Update open mode initialization: line fault (overload or shortcircuit) at power on.
Check the electrical connections among the circuit module and the points connected directly
with LA and LB.
102
Update open mode initialization: lack of 4 consecutive addresses to assign to a multiple I/O
module.
106
Update open mode initialization: missing answer from a point with valid (1–128) address.
The module could not communicate with the point: check the electrical connections.
Summary of Contents for FAP54
Page 8: ...8 FAP54 Installation 2 5 LAYOUT OF FAP54 01 INTERNAL MODULES ...
Page 9: ...FAP54 Installation 9 2 6 LAYOUT OF FAP54 04 INTERNAL MODULES ...
Page 10: ...10 FAP54 Installation 2 7 LAYOUT OF FAP54 08 INTERNAL MODULES ...
Page 11: ...FAP54 Installation 11 2 8 LAYOUT OF FAP54 16 INTERNAL MODULES ...
Page 12: ...12 FAP54 Installation 3 FAP54 COMPONENTS 3 1 FRONT PANEL OF FAP541 ...
Page 39: ...FAP54 Installation 39 ...