16
FAP54 Installation
3.5 FAP ELECTRICAL SPECIFICATIONS
AC mains
100-240 V~ -15/+10%, 50/60 Hz, 3 A
Current consumption
I min:
I max a:
0.4 A control panel only and line modules
4.85 A
Maximum and minimum electrical
characteristics for each input and output:
Output voltage variation (V OUT):
Minimum output voltage (V OUT):
Output voltage ripple (V OUT):
23 V
⎓
÷ 26 V
⎓
18.4 V
⎓
(nominal load and mains disconnected)
160 mVpp
Detection circuit:
Maximum current to be used for detection lines:
20 V nominal, max 100 mA (limited to 400 mA)
1.5 A
Batteries:
Maximum usable battery:
Batteries fuse:
Maximum current provided by batteries with AC
power supply disconnected:
Maximum battery internal resistance:
2x12V 12 Ah
F4AL 250V
4.0 A
Rimax 0.8
Ω
Operating temperature:
-5°C ÷ +40°C
Pollution grade:
Grade 2
Overvoltage category:
CAT II
NA/NC outputs:
Fire alarm
Siren activated
Faults
Programmable (Missing AC / Exclusions)
Controlled outputs:
Siren (max 500mA)
Self-powered siren (max 250 mA)
RS232/RS485:
USB:
LAN:
MODEM:
KEYBOARD:
REMOTE PANEL:
RS485 opto-isolated RS485 (optional)
USB USB host (connection with mass storage USB key)
Ethernet (10/100 Mbit , RJ45 connector) optional
Modem PSTN/GSM optional
Connector for PS2 keyboard
Terminal blocks for connection to a 1043/534 remote panel
Symbol
Meaning
Direct current voltage
Refer to the installation manual
Summary of Contents for FAP54
Page 8: ...8 FAP54 Installation 2 5 LAYOUT OF FAP54 01 INTERNAL MODULES ...
Page 9: ...FAP54 Installation 9 2 6 LAYOUT OF FAP54 04 INTERNAL MODULES ...
Page 10: ...10 FAP54 Installation 2 7 LAYOUT OF FAP54 08 INTERNAL MODULES ...
Page 11: ...FAP54 Installation 11 2 8 LAYOUT OF FAP54 16 INTERNAL MODULES ...
Page 12: ...12 FAP54 Installation 3 FAP54 COMPONENTS 3 1 FRONT PANEL OF FAP541 ...
Page 39: ...FAP54 Installation 39 ...