![ELKHART BRASS Copperhead RF 8593-04 Installation, Operating, & Maintenance Instructions Download Page 5](http://html1.mh-extra.com/html/elkhart-brass/copperhead-rf-8593-04/copperhead-rf-8593-04_installation-operating-and-maintenance-instructions_2393091005.webp)
6
SYSTEM COMPONENTS
MONITOR
Copperhead RF Monitor – 8593-04
The 8593-04 Copperhead RF is a brass monitor that contains a central
vane inside the waterway to minimize large-scale turbulence and
provide superior fire streams. The water supply is provided through the
monitor base by a 3” 150# flat faced flange. The discharge nozzle
connection is a 2½“ National Hose Thread. Nozzle stream direction is
controlled by two permanent magnet type gear motors, one controlling
rotation about the axis of the water inlet, and the other controlling
nozzle elevation and depression.
Max Flow:
1250 GPM (4732 LPM)
Weight:
74 Lbs
8593-04 Copperhead RF
(P/N: 08593041)
Caution:
All monitor motors are 12VDC. If using a non-Elkhart nozzle, another 12VDC
nozzle should be used, or nozzle control may not function properly.
NOZZLE
Copperhead RF Nozzles –
There are two nozzles recommended for the Copperhead RF.
SM-1250BE
The maximum monitor flow capacity is 1250 gallons per minute.
Monitors can be supplied with the SM-1250BE constant pressure
(automatic) type master stream nozzle. This nozzle has a flow range of
300 to 1250 gallons per minute at 75 psi and has an electric drive
mechanism for RF control of the spray pattern from a straight stream to
wide fog.
SM-1250BE;
300 GPM @ 50 PSI – 1250 GPM @ 75 PSI
181 Deluge & 282-B Stream Shaper
Pairing the 282-B stream shaper with the 181 brass
smooth bore ensures great stream quality with the flow
of a smooth bore nozzle.
SM-1250BE (P/N: 03782201)
181 Deluge (P/N: 66687001) &
282-B (P/N: 03476102)