SYSTEM SPECIFICATIONS
Panel Mount Controller
Input power
12/24 VDC (11 VDC to 30 VDC)
RF power output
Meets FCC part 15 requirements for license free operation
Transmitter dimensions
7 5/8” x 3 7/8” x 2 3/8”
Operating temperature range
-40
o
C to +65
o
C, -40
o
F to +150
o
F
Environmental Rating
NEMA 4
FCC ID
QT8PTSS2011
Handheld Controller
Input power
2 AA Batteries (Lithium Recommended)
RF power output
Meets FCC part 15 requirements for license free operation
Transmitter dimensions
6” x 3 1/4” x 1 3/8”
Transmitter weight
10 ½ oz.
Operating temperature range
-40
o
C to +65
o
C, -40
o
F to +150
o
F
Environmental Rating
NEMA 4
FCC ID
QT8PTSS2011
Receiver
Power requirements
Without Converter Assembly 12VDC (11-14VDC)
With Converter Assembly (11-30VDC)
at the controller under full load
Electrical Load
See Table 4 Below
Control current
0.07 A (12V)
Operating temperature range
-40
o
C to +65
o
C, -40
o
F to +150
o
F
Environmental Rating
NEMA 4
Monitor
Left/Right
Up/Down
Nozzle
Run Current*
4.3 A
4.8 A
0.7 A
Stall Current*
14 A
14 A
NA
Current Trip Point*
12.5 A
8 A
4 A
Table 4: Motor Current Specifications
*All current ratings are at 12V
Shock
30 G’s (55 Hz. @ .2” double amplitude)
Vibration
15.5 G’s (55 Hz. @ .05” double amplitude) continuous operation
Drop Test
The handheld controller must meet operating specifications after drop from 1m height onto
concrete surface.
Environmental
All enclosures have a NEMA 4 rating (must withstand a 1” stream of water at 65 GPM from a
distance to 10ft. for five minutes with no water entering the enclosure).