background image

M1XSLZW   Instruction Manual

Page 9

How to setup Z-Wave Groups using a terminal emulator such as Hyperterminal

It is not currently possible to set up Z-Wave lighting nodes into Z-Wave lighting groups using the LEVITON Vizia RF Installer Tool and 

PC Software.  The following is a simple but effective workaround to the missing capability in the Leviton tools.  It consists of using 

a terminal emulator program such as Hyperterminal to send ASCII strings over RS232 from the PC to the Serial Interface (VRC0P) 
Controller.  These ASCII strings contain the node ids and group assignments.  Although the task is fairly straightforward, it does require 
all the Z-Wave nodes to previously been setup and working.

After Z-Wave nodes have been setup into groups the Elk-M1XSLZW Z-Wave Interface can then send Z-Wave Group commands.  

NOTE: Setup the Z-Wave network before executing the steps below.  The ID numbers of the working Z-Wave Node must be known.

Requirements needed prior to setting up Z-Wave lighting nodes into Z-Wave lighting groups:

1.  A PC terminal emulator program such as Hyperterminal.  Other comparable programs might also be suitable.

2. 

A standard RS232 serial port on the PC.  If the PC only has a USB port then a suitable USB to RS232 converter cable is required. 

3.  A Leviton RS232 Serial Interface (VRC0P) Controller.  This is the controller being used with the Elk-M1XSLZW.  Temporarily 

disconnect it from the Elk-M1XSLZW and connect it directly to the PC serial or USB/serial cable.

4.  Make a listing of the Groups to be setup including a number from 1 to 64 and a descriptive name. 

5.  Make a listing of the existing Z-Wave nodes IDs that are to be setup into the identified groups.  The Node ID MUST be known!

Setup

6.  Connect the PC to the VRC0P using the serial or usb/serial converter cable.

7.  Open the terminal emulator (Hyperterminal) software.

8.  Check the serial connection settings and verify they are set as follows:
 

 

UART Settings: 9600 Baud rate, 8 Data bits, No Parity, 1 Stop bit, No Flow Control

 

 

Properties -> ASCII Setup-> “Send line ends with line feeds=Yes” and “Echo type characters locally=Yes”

9.  Locate and click the command or ICON for “Connect” to establish a connection to the VRC0P Controller.  If the connection is 

successful it will be possible to see feedback coming from the VRC0P whenever a Z-Wave device is manually controlled.

10.  Format and entry requirements for the Text Strings:
 

 

All typed characters must be UPPERCASE

 

 

Each string must start with the characters:  >N

 

 

Follow the >N with the appropriate Node IDs separated with a comma between each ID. 

 

 

Do not type a comma after the last Node ID.

 

 

Follow the last Node ID with the characters: GS

 

 

Follow the GS with a number from 1 to 64 corresponding to the desired Group number.

 

 

Click the carriage return key to transmit the string to the VRC0P.

 

ASCII string example for Group 1:   

>N1,2,3,4GS1

 {return} will setup Nodes 1, 2, 3, and 5 into lighting group 1.

 

The group 1 can now be manually testing by typing two more strings into Hyperterminal.  Each must be a separate line.

 

 

 

>GR1 {enter}   

 

 

 

>ON {enter}    Nodes 1, 2, 3, and 4 should all turn ON.   Substitute >OFF {enter} to turn the group off.  

11.  The serial interface controller performs a simple error checking and should respond with <E000 = No error.   If a response other 

than <E000 is received then check the string for compliance with the formatting in step 10.  Make sure that all Nodes IDs are 
valid.

12.  Once all groups have been setup unplug the serial interface from the PC and plug it back into the M1XSLZW Interface.  Power 

cycle the M1XSLZW and allow it time to autodiscover all the new groups.

13.  Program the ElkRP rules to activate the groups that have just been setup.

An example of a rule to control Group 1 from the M1:

   

WHENEVER FRONT DOOR (ZNxx) BECOMES NOT SECURE

   

 

THEN TURN LIGHT 129 ON    {Light 129 corresponds to Group 1)  Nodes 1, 2, 3, and 4 should all turn ON.

   

WHENEVER FRONT DOOR (ZNxx) BECOMES SECURE

   

 

THEN TURN LIGHT 129 OFF    {Light 129 corresponds to Group 1)  Nodes 1, 2, 3, and 4 should all turn OFF.

Summary of Contents for ELK-M1XSLZW

Page 1: ...3 is known as a Z Wave Secondary Controller It is required as a permanent member of the Z Wave network to maintain contact with all Z Wave devices and communicate via RS232 to the M1XSLZW The M1XSLZW...

Page 2: ...viton web site links http www leviton com OA_HTML ibeCCtpSctDspRte jsp section 25545 minisite 10024 http communities leviton com docs DOC 2389 http communities leviton com community knowledgebaseforum...

Page 3: ...The Dimmers will not react to a button press if not associated NOTE Not all Z Wave devices support full association Update Controller Updating transfers existing Node ID information associations rout...

Page 4: ...61 62 63 64 Name or Description of Device This page is provided for listing all the Z Wave Devices their names and device types Device Type Z Wave Node ID 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79...

Page 5: ...24hours Next turn on the M1 Master Power Switch which will then supply power to the M1XSLZW 7 Enroll the M1XSLZW to the M1 Control REQUIRED This is done either via a Keypad or ElkRP Software From a Ke...

Page 6: ...a new Rule E G Turn OFF several Z Wave Lights when the System is Armed Away 3 13 Click WHENEVER Security Alarms Is Armed Armed Away A pop up box appears to pick the Area partition Use the drop down t...

Page 7: ...A16 17 B1 18 B2 19 B3 20 B4 21 B5 22 B6 23 B7 24 B8 25 B9 26 B10 Z Wave Node ID 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 ELK Lighting Device 27 B11 28 B12 29 B13...

Page 8: ...k mark in the Show box IF the Group will need to be displayed on touchscreens or keypads 4 10 Voice Description is optional Up to 6 words may be used to provide a spoken description for each Group Con...

Page 9: ...ify they are set as follows UART Settings 9600 Baud rate 8 Data bits No Parity 1 Stop bit No Flow Control Properties ASCII Setup Send line ends with line feeds Yes and Echo type characters locally Yes...

Page 10: ...ustomer wants the Thermostats to appear in a desired order then it will be necessary to perform the Z Wave Inclusion in exactly that desired order That s because the order of mapping in M1 is based so...

Page 11: ...elow 5 12 To set the Cooling setpoint click THEN Thermostat 5 13 Select the same Thermostats E G Main Hallway Tstat 1 as before 5 14 Click Set cooling desired temperature to 5 15 In the value box scro...

Page 12: ...a THEN Send Text to Port X command in an ElkRP Rule The Text will be your command and the Port X will be the Data Bus Address of the M1XSLZW Mapping of the locks is done by the M1XSLZW on power up usi...

Page 13: ...result each lock command will require a dedicated rule In addition no other THEN commands should exist in a rule that is being used for Locks Z Wave Locks use a special encrypted Security Class for c...

Page 14: ...nts of low battery alert through the use of automation rules and special text strings This new capability was added in M1XSLZW firmware version 81 0 4 1 Select ElkRP Automation Texts and add the follo...

Page 15: ...ity or operation of electronic locks It is the sole responsibility of the Installing Company or Individual to use best judgment when remotely controlling or automating door locks CONFIRMING LOCK STATU...

Page 16: ...or 1 as soon as exit delay expires following System Arming Rule 7 Locks door 1 just as soon as Front Door closes following System Arming The door will get locked no matter whether Rule 6 or 7 fires fi...

Page 17: ...text TPOLL M DO NOT use the polling if not absolutely necessary as it does create excessive traffic XPOLL M Text string XPOLL M informs the M1XSLZW to stop the timed polling of Thermostats if enabled...

Page 18: ...M1XSLZW Instruction Manual Page 18 PO Box 100 3266 US Hwy 70 West Hildebran NC 28637 828 397 4200 828 397 4415 Fax http www elkproducts com...

Reviews: