SX - Operating- & Service instruction - 8 074 667.02/02 - page 45
Trip messages
The frequency inverters are equipped with protection functions against overcurrent, overvoltage, undervoltage a.s.o.
If a protection function is engaged, the output voltage is shut down, motor coast to a halt and the inverter holds this condi-
tion until it is reset.
Trip message Description
Cause
Remedy
E1, E31
Overcurrent or overtemperature Is the nom. motor current higher Select a bigger frequency
in the power module in a
than the nom. inverter current ? inverter.
static condition
Was there a sudden load
Avoid sudden overloads
increase or is the motor
or select a bigger frequency
stalled ?
inverter and motor.
Are the motor terminals
Check if motor cables and/or
U, V, W short circuited ?
the motor are short circuited.
E3 , E33
Overcurrent or overtemperature Is the acceleration time adjusted Increase the acceleration time.
in the power module
too short ?
during acceleration
Are the motor terminals
Check if motor cables and/or
U, V, W short circuited ?
the motor are short circuited.
Is the voltage boost F8
Decrease F8.
adjusted too high ?
Is the motor stalled ?
Check motor load and the
starting torque.
E2, E32
Overcurrent or overtemperature Is the deceleration time
Increase deceleration time.
in the power module
adjusted too short ?
during deceleration
Are the motor terminals
Check if motor cables and/or
U, V, W short circuited ?
the motor are short circuited.
Is the braking unit damaged ?
Check the braking unit.
E4, E34
Overcurrent or overtemperature Is the allowed ambient
Check the ambient
in the power module
temperature exceeded ?
temperature.
during stand still
E5
Internal motor protection
The internal electronic motor
Select a bigger frequency
is engaged
protection has engeged due
inverter and motor or check
to an overload of the
the adjustment of the electronic
connected motor
motor protection.
The frequency inverter is in
The output current is higher
Select a bigger frequency
an overload condition
than the nom. inverter current
inverter.
E6
The braking duty (adjusted via
Is the deceleration time
Increase deceleration time.
A38) is exceeded
adjusted too short ?
(ELVO
vert
SX 5,5 kW and
7,5 kW only)
Is the duty time adjusted
Increase the duty time.
too low ?
E7
DC-link overvoltage
The motor was operated
Tieflaufzeit verlängern
regenerative
Deceleration time ?
Use a braking unit and/or
braking resistors.
Summary of Contents for ELVOvert SX
Page 1: ...8074667 02 02 ELVOvert SX Operating Service Projecting Mounting Connecting...
Page 4: ...SX Operating Service instruction 8 074 667 02 02 page 2 Notes...
Page 28: ...SX Operating Service instruction 8 074 667 02 02 page 26 Notes...
Page 52: ...SX Operating Service instruction 8 074 667 02 02 page 50 Notes...