SX - Operating- & Service instruction - 8 074 667.02/02 - page 47
Trip message Description
Cause
Remedy
E19
Error on the optional card 1
A trip has occured on the
Reset.
optional card 1
E20
Error on the optional card 2
A trip has occured on the
Reset.
optional card 2
E24
Phase failure
One phase of the input
Check the input voltage.
voltage is missing or the
input voltage was shut off
during deceleration
No
Inverter keypad display does
Due to a malfunction of the
Check the fuse DP12 on the
display
not appear and power charge
MOSFET on the power
power supply PCB and
lamp does not light after
supply PCB the fuse DP12
replace it if necessary.
power ON
(glass tube, 250 V, 2 A) has
been damaged or is blown.
Trip messages can be reset. There are the following possibilities:
Reset via input RS
Reset via the STOP/RESET key on the keypad
Mains switch-off
Remark: An inverter which operates without any failure will decelerate to 0 Hz, if an reset signal is released !!
Remark: An inverter which operates without any failure will decelerate to 0 Hz, if an reset signal is released !!
If the failure message remains after performing a reset,
If the failure message remains after performing a reset,
please call a technician or the supplier of the unit service.
please call a technician or the supplier of the unit service.
Summary of Contents for ELVOvert SX
Page 1: ...8074667 02 02 ELVOvert SX Operating Service Projecting Mounting Connecting...
Page 4: ...SX Operating Service instruction 8 074 667 02 02 page 2 Notes...
Page 28: ...SX Operating Service instruction 8 074 667 02 02 page 26 Notes...
Page 52: ...SX Operating Service instruction 8 074 667 02 02 page 50 Notes...