21
USER MANUAL TPS/M 62000595 REV 03_
–
01/06/2021
2.2.3.
MAGNETO-THERMAL PROTECTION
The Magneto-thermal circuit breaker protect the line from short circuits. Generally depends on
the load and on the connection (section and length of the cable).
It is recommended to use a magneto-thermal protection with
type C
curve according to the
nominal characteristic (see section 1.2).
2.2.4.
LINE FUSES
Fuses can be used to protect power line of the TPS. It's recommended to use delayed fuses
according to the nominal input characteristic (see section 1.2).
2.2.5.
INTERNAL FUSES TPS/M/D 1K5
Item
Name
Description
Size
Current Type Voltage
1
F1
Mainline Input
10x38 16A
GL
500V
2
F2
Safety Circuit
5x20
1.25A
AT
250V
3
F4
Aux Supply
5x20
3.15A
AT
250V
The layout may be different and depends the model design
2.2.6.
INTERNAL FUSES TPS/M/D 3K
Item
Name
Description
Size
Current Type Voltage
1
F1
Mainline Input
10x38 25A
GL
500V
2
F2
Safety Circuit
5x20
1.25A
AT
250V
3
F4
Aux Supply
5x20
3.15A
AT
250V
The layout may be different and depends the model design
2.2.7.
INTERNAL FUSES TPS/M/D 6K
Item
Name
Description
Size
Current Type Voltage
1
F1, F2, F3
Mainline Input
10x38 16A
GL
500V
2
F4
Input Aux supply
10x38 1A
AM
400V
2
F5
Aux Supply
5x20
3.15A
AT
250V
3
F6
Safety Circuit
5x20
1.25A
AT
250V
The layout may be different and depends the model design
Summary of Contents for TPS/M/D
Page 1: ...1 USER MANUAL TPS M 62000595 REV 03_ 01 06 2021 TPS M D USER MANUAL ...
Page 13: ...13 USER MANUAL TPS M 62000595 REV 03_ 01 06 2021 1 4 3 TPS M D 6KVA 281 513 ...
Page 14: ...14 USER MANUAL TPS M 62000595 REV 03_ 01 06 2021 1 4 4 TPS M D 9KVA 281 513 ...
Page 25: ...25 USER MANUAL TPS M D 62000447 REV 00_ 31 08 2021 2 3 2 4 WIRE CONFIGURATION TPS M D TPS M D ...
Page 36: ...36 USER MANUAL TPS M D 62000447 REV 00_ 31 08 2021 Limitations is enable both AC and DC mode ...