OPERATING STATUS DISPLAY
Report
Description
Measure to solve the problem
Safety open limit operated
Turn mains supply OFF and move the shutter
downwards - with the manual operator- until the
safety limit is free or the open limit should be re-
adjusted.
Safety close limit operated
Turn mains supply OFF and move the shutter upwards
- with the manual operator- until the safety limit is
free or the close limit should be re-adjusted.
Door load monitor has acti-
vated
Check the door mechanism for tightness
ROM - Fault
Internal fault report
RAM - Fault
Internal control fault
DES – no response
Drive unit does not work
Check the shutter mechanics. Check the limit shaft
for function (turning) Check phase rotation.
Phase rotation failure
Check main supply phase rotation turns right
Check electronic limit DES connection. To
acknowledge the fault; switch OFF/ON on the mains
or disconnect and reconnect the mains plug. If
necessary replace the control panel. If necessary
replace the control panel or digital limit DES).
To acknowledge the fault; switch OFF/ON on the mains
or disconnect and reconnect the mains plug.
If necessary replace the control panel.
To acknowledge the fault; switch OFF/ON on the mains
or disconnect and reconnect the mains plug.
If necessary replace the control panel.
To acknowledge the fault; switch OFF/ON on the mains
or disconnect and reconnect the mains plug.
If necessary replace the control panel.
To acknowledge the fault; switch OFF/ON on the mains
or disconnect and reconnect the mains plug.
If necessary replace the control panel.