Page 70 KSSSI116
Communication Fault Continues:
# Disconnect the supply power & check the
continuity
of the COM-U wire from the following
points:
COM-U terminal point on the indoor PCB.
To the communication terminal points on the indoor terminal block.
To the communication terminal points on the outdoor terminal block.
To the COM-U terminal point on the outdoor PCB.
Note:
When checking the
continuity
between the indoor terminal block & the outdoor terminal
block, disconnect the COM-U & Active wires on the indoor terminal block, and then attach them
together. This will create a
circuit
that can then be tested between the COM-U & Active terminal
points on the outdoor terminal block.
COM-U terminal point on indoor PCB.
Communication terminal points on
indoor terminal block.
Communication terminal points on outdoor
terminal block.
COM-U terminal point on outdoor main PCB.
Summary of Contents for KSV26HRC
Page 10: ...Page 10 KSSSI116 Electrostatic Discharge ...
Page 11: ...Page 11 KSSSI116 ...
Page 12: ...Page 12 KSSSI116 ...
Page 30: ...Page 30 KSSSI116 KSV26CRC KSV26HRC Outdoor Unit mm KSV35CRC KSV35HRC Outdoor Unit mm ...
Page 31: ...Page 31 KSSSI116 Dimensions KSV53HRC Indoor Unit mm ...
Page 32: ...Page 32 KSSSI116 KSV53HRC Outdoor Unit Unit mm ...
Page 34: ...Page 34 KSSSI116 Outdoor Unit KSV62HRC Unit mm KSV70CRC KSV70HRC KSV80HRC Unit mm ...
Page 110: ...Page 110 KSSSI116 Wiring Diagrams KSV26 35 53CRC HRC Indoor ...
Page 111: ...Page 111 KSSSI116 KSV62 70 80CRC HRC Indoor ...
Page 112: ...Page 112 KSSSI116 KSV26 35CRC Outdoor ...
Page 113: ...Page 113 KSSSI116 KSV26 35HRC Outdoor ...
Page 114: ...Page 114 KSSSI116 KSV53 62HRC Outdoor ...
Page 115: ...Page 115 KSSSI116 KSV70CRC Outdoor ...
Page 116: ...Page 116 KSSSI116 KSV70 80HRC Outdoor ...
Page 133: ...Page 133 KSSSI116 ...