Dry Mode:
Drying Conditions and Process (KSV53, 62, 70 & 80CRC/HRC)
When (indoor ambient temperature - Tamb.) is above (indoor preset temperature - Tpreset), the unit operates in cooling
mode, with the compressor and outdoor fan in operation. Indoor fan operates at set fan speed (low fan speed, quiet fan
speed).
When (indoor ambient temperature - Tamb.) is -3ºC below (indoor preset temperature - Tpreset), compressor, outdoor
fan and indoor fan operate at set fan speed (low fan speed, quiet fan speed).
Under this mode, the temperature setting range is 16
~
30
℃
. Display displays operation icon, drying icon and set
temperature.
Summary of Contents for KSV26HRC
Page 10: ...Page 10 KSSSI116 Electrostatic Discharge ...
Page 11: ...Page 11 KSSSI116 ...
Page 12: ...Page 12 KSSSI116 ...
Page 30: ...Page 30 KSSSI116 KSV26CRC KSV26HRC Outdoor Unit mm KSV35CRC KSV35HRC Outdoor Unit mm ...
Page 31: ...Page 31 KSSSI116 Dimensions KSV53HRC Indoor Unit mm ...
Page 32: ...Page 32 KSSSI116 KSV53HRC Outdoor Unit Unit mm ...
Page 34: ...Page 34 KSSSI116 Outdoor Unit KSV62HRC Unit mm KSV70CRC KSV70HRC KSV80HRC Unit mm ...
Page 110: ...Page 110 KSSSI116 Wiring Diagrams KSV26 35 53CRC HRC Indoor ...
Page 111: ...Page 111 KSSSI116 KSV62 70 80CRC HRC Indoor ...
Page 112: ...Page 112 KSSSI116 KSV26 35CRC Outdoor ...
Page 113: ...Page 113 KSSSI116 KSV26 35HRC Outdoor ...
Page 114: ...Page 114 KSSSI116 KSV53 62HRC Outdoor ...
Page 115: ...Page 115 KSSSI116 KSV70CRC Outdoor ...
Page 116: ...Page 116 KSSSI116 KSV70 80HRC Outdoor ...
Page 133: ...Page 133 KSSSI116 ...