RU Flex 2100 DLS Specifications
Measurement Length:
Available from 2 to 48 feet in length
Tubing Material:
UHMW-PE
Float: Nitrophyl/stainless steel
One float used for single liquid level measurement; two floats used for 2 liquids
Two-piece floats for field installation and replacement
Designed to fit though a 3-inch NFPT tank port
Level Measurement Increments and Accuracy:
1/8-in. resolution; +/- 3/16-in. accuracy
1/4-in. resolution; +- 1/8-in. accuracy
1/2-in. resolution; +/- 1/4-in. accuracy
+/- 0.1% repeatability
Coiled Diameter:
Approximately 36-inch diameter (will vary slightly with the length of the sensor)
Operating Temperature Range:
-40° C to +85° C
Temperature Measurement:
First sensor 14” from bottom
Up to 8 temperature sensors available with desired spacing: optional
+/- 1.5° C accuracy
Power Requirements:
5.6 VDC to 13 VDC
Power Consumption:
15mA nominal
20mA maximum
Pressure:
40 psi: standard
Communication:
RS485
Two- or four-wire communications
Baud rate and parity programmable (up to 57600 baud on v.3.15 and higher)
4-20mA signal available when connected to digital-to-analog converter board
Wireless capable