10-26
CONTROL SYSTEM
Revision Y05-01
Service Manual - MOBILE Series
10.11
Forced Operation
Forced operation allows units to start, stop and operate in Cooling or Heating in pre-set
temperature according to the following table:
Forced operation
mode
Pre-set Temp for ;
MBX, P2000, PRX,
PX, PXD models
Pre-set Temp for :
FCD, RWK, ELD, ECC,
WAX, WMF, WMN, WNG
models
Cooling
20
°
C
22
°
C
Heating
25
°
C
28
°
C
Note:
•
While under the forced operation, the temperature compensation
schedule.
•
The forced operation is activated when the mode button on the
Display Board is used to switch the unit to Cool or Heat mode.
•
The IFAN is always set to Autofan Speed in forced operation.
Summary of Contents for Monoblock 7
Page 26: ...8 3 WIRING DIAGRAMS Revision Y05 01 Service Manual MOBILE Series 8 3 SP 11 16 Electronic Model...
Page 27: ...8 4 WIRING DIAGRAMS Revision Y05 01 Service Manual MOBILE Series 8 4 SP 11 16 Mechanical Model...
Page 32: ...10 3 CONTROL SYSTEM Revision Y05 01 Service Manual MOBILE Series 10 3 Main PCB Controller...
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 169: ...QUICK CONNECTORS APPLICATION OPTIONAL English 10...
Page 186: ...P2000 SPLIT CAT NO 453125500 MULTILANGUAGE REV 01 11 2004...