1.5.5 - Parameter settings in the programming menu
PARAMETER
UNIT
RANGE
SET VALUE
DELAY
BASE PARAMETERS
B01 - Rated Voltage Phase - Neutral
Volt
80 - 480
230
B02 - Rated Voltage Phase - Phase
Volt
80 - 600
400
B03 - Rated frequency
1 - 50Hz
2 - 60Hz
1 - 50Hz
B04 - Type of connection
1 - Single-phase
2 - Split phase
3 - 3Ph
4 - 3Ph + N
5 - Auto detect
4 - 3F + N
Star Connection
B05 - Format of units of measurement
1 - Metrics
2 - US
1 - Metrics (bar, °C)
B06 - AMF mode (automatic start of G.S. when the main fails)
1 - Disabled
2 - Enabled
2 - Enabled
B07 - Delay for power saving mode MC2 module (only with AMF
function disabled)
min
0 - 360
2
B08 - Tower light mode (only with AMF function disabled)
1 - Disabled
2 - Enabled
1 - Disabled
B09 - Rated engine r.p.m.
RPM
100 - 4000
1500
PARAMETERS AND ENGINE PROTECTIONS
E01 - Pre-start time
Sec.
0 - 600
5
E02 - Maximum supply time for starter motor
Sec.
0 - 60
5
E03 - Cooling time
Sec.
0 - 3600
30
E04 - Shutdown for low oil pressure
Bar
0 - 10
0,6
3s
E05 - Shutdown for high coolant temperature
°C
0 - 150
95
5s
E06 - Battery undervoltage
Vdc
0 - 40
11.5
30s
E07 - Remaining hours to maintenance*
h
0 - 10000
250
E08 - Release of the starter motor from low oil pressure
1 - Disabled
2 - Enabled
1 - Disabled
E09 - Choke time (only for petrol engines)
Sec.
1 - 3600
0
E10 - Stabilization time before closing the RG contactor
Sec.
1 - 300
5
E15 - Shutdown due to low fuel level
%
0 - 20
10
10s
ALTERNATOR PROTECTIONS
G01 - Shutdown due to overvoltage
%
G02 - 200%
110
3s
G02 - Shutdown due to under voltage
%
0% - G01
80
3s
G03 - Shutdown due to high frequency
%
G04 - 130%
110
3s
G04 - Shutdown due to low frequency
%
0% - G03
90
3s
AMF SETTINGS
(G.S. starts automatically when the main fails)
A01 - Start delay for mains failure
Sec.
0 - 600
5
A02 - Mains stabilization time when the mains come back
Sec.
1 - 3600
20
A03 - Overvoltage mains
%
A04 - 150%
110
0.1s
A04 - Undervoltage mains
%
50% - A03
80
0.1s
A05 - Overfrequency mains
%
A06 - 150%
102
0.1s
A06 - Underfrequency mains
%
50% - A05
98
0.1s
*To reset the remaining hours to the next maintenance, enter the programming menu (See 1.5.3), select
then add the correct
number of remaining hours to the next maintenance, by entering the parameter
E07
.
User and Maintenance Manual