Technical data
5
R601 R602 R603 R604 R605 R606 R607
Nominal heat output at 80/60ºC max/min*
kW
142.1/23.3 190.1/39.5 237.2/39.5 285.2/39.5 380.2/76.6 475.3/76.6 539.0/76.6
Nominal heat output at 75/60ºC max/min*
kW
142.2/23.5 190.3/39.5 237.4/39.5 285.5/39.5 380.6/76.6 475.8/76.6 539.6/76.6
Nominal heat output at 40/30ºC max/min*
kW
150.7/26.7 201.6/45.2 251.4/45.1 302.3/45.2 403.1/87.7 503.9/87.7 571.5/87.7
Nominal heat input Hi max/min*
kW
145.0/24.5 194.0/41.5 242.0/41.5 291.0/41.5 388.0/80.5 485.0/80.5 550.0/80.5
Efficiency at 80/60ºC
% 98.0
Efficiency at 40/30ºC
% 103.9
Annual efficiency (NNG 75/60ºC)
% 106.8
Annual efficiency (NNG 40/30ºC)
% 110.4
Standstill losses (T
water
= 70ºC)
% 0.21 0.18 0.17 0.16 0.15 0.14 0.13
Max. condensate flow
l/h 11 15 19 22 30 37 42
Gas consumption H-gas max/min (10,9 kWh/m
3
)
m
3
/h 13.3/2.3 17.8/3.8 22.2/3.8 26.7/3.8 35.6/7.4 44.5/7.4 50.5/7.4
Gas consumption L-gas max/min (8,34 kWh/m
3
)
m
3
/h 17.4/2.9 23.2/5.0 29.0/5.0 34.9/5.0 46.5/9.7 58.2/9.7 66.0/9.7
Gas consumption LL-gas max/min (8,34 kWh/m
3
)
m
3
/h 17.4/2.9 23.2/5.8 29.0/5.8 34.9/5.8 46.5/11.2
58.2/11.2
66.0/11.2
Gas consumption LPG. max/min (12,8 kWh/kg)
kg/h 11.3/1.9 15.2/3.2 18.9/3.2 22.7/3.2 30.3/6.3 37.9/6.3 43.0/6.3
Gas pressure H-gas
mbar 20
Gas pressure L/LL-gas
mbar 25
Gas pressure LPG
mbar 30/50
Maximum gas pressure
mbar 100
Flue gas temperature at 80/60ºC max/min
ºC 78/61
Flue gas temperature at 40/30ºC max/min
ºC 56/30
Flue gas quantity max/min*
m
3
/h 238/40 318/69 397/69 477/69 636/134
795/134
901/134
CO
2
level natural gas H/E/L/LL max/min
% 10.2/9.4
CO
2
level liguid gas P max/min
% 11.9/10.0
NOx level max/min
mg/kWh 35/15
CO level max/min
mg/kWh 14/8
Max. permissible flue resistance max/min
Pa 160/10 160/10 200/10 200/10 200/10 250/10 250/10
Water volume
l 27 31 35 61 68 75 82
Water pressure max/min
bar 8/1
Max. water temperature (High limit thermostat)
ºC
100
Maximum temperature setpoint
ºC 90
Nominal water flow at dT=20K
m
3
/h 6.1 8.1 10.2 12.2 16.3 20.4 23.1
Hydraulic resistance at nominal water flow
kPa
10 18 28 15 27 42 55
Electrical connection
V 230/400
Frequency
Hz 50
Mains connection fuse
A 16
IP class
- IP20
Power consumption boiler max/min (excl. pump)
W 158/43 200/35 230/35 260/35 470/61 650/61 770/61
Power consumption 3-step pump (optional)
W 170/90
190/120
380/210
380/210
530/300
720/380
1150/600
Power consumption speed controlled pump (opt)
W 180/10 180/10 435/25 435/25 450/25 800/35 800/35
Power consumption bypass pump (optional)
W 55/35 85/65
170/90
170/90
190/120
460/225
470/280
Weight (empty)
kg 295 345 400 465 535 590 650
Noise level at 1 meter distance
dB(A)
59
Ionisation current minimum
µA
6
PH value condensate
-
3.2
CE certification code
-
CE-0063BS3840
Water connections
-
R2"
DN65 PN16
Gas connection
- R3/4" R1" R1" R1" R1.1/2"
R1.1/2"
R1.1/2"
Flue gas connection
mm 150 150 200 200 250 250 250
Air intake connection (for room sealed use)
mm 130 150 150 150 200 200 200
Condensate connection
mm
40 40 40 40 40 40 40
* min load on gasses H/L/LPG. For type R602-R607 on gasses LL-Gas min value is 15% higher.
Summary of Contents for Bypass R600
Page 2: ......
Page 34: ......
Page 35: ...Betriebsanleitung für die autorisierte Fachkraft R 600 07 2010 DOC3070 12099579 ...
Page 66: ......
Page 98: ......
Page 119: ...21 21 Bedienung Description du display Programmation ...
Page 130: ......
Page 131: ...Istruzioni per l uso solo per il tecnico autorizzato R 600 07 2010 DOC3070 12099579 ...
Page 151: ...21 Guida all uso Descrizione del display Programmazione ...
Page 162: ......
Page 163: ......