Collector assembly
Installing the collector sensor;
connecting the collector panel
Installing the collector sensor
•
Insert the collector sensor into the
sleeve in the basic module before
assembling the tubes and before in-
stalling the connecting pipes. The
thermowell attaches to the tubing
inside the manifold. Use thermally
conductive paste. The paste is not
included in the scope of supply. Seal
the sensor using a PG connection.
Make sure the sensor cables do not
become twisted. You should no long-
er be able to pull it out after tightening
the connector.
Connecting the collector panel
•
Connect the collector panel to the
prepared piping using flexible hoses.
Return connection: COLD
Supply connection: HOT
Use a counter-wrench when mount-
ing the fittings! Ensure that the man-
ifold tubing does not turn while tight-
ening the fittings.
A air trap shall be located at the
highest point. If there is an air sepa-
rator, it shall be located in the base-
ment.
If no air separator is installed in the
basement, a system vent with air trap
shall be installed at the highest point in
the system. It shall be remotely con-
trolled if necessary.