BEA--250127-EN-09
15/22
ELMETA
®
MDS 50
The field
Number
of the table shows the parameter number, the field
Name
the respective abridged designation. The field
Default
shows
the standard settings,
Min
and
Max
are the acceptable limit values.
The field
Access
specifies whether a parameter may just be read (R)
or read and written (R/W). The field
Explanation
describes the func-
tion of the parameter.
Number Name
Default Min
Max Access Explanation
0
edit device
X.X
X.1
X.F
R/W
Select equipment number (see block diagram)
1
edit group
X.X
0.X
7.X
R/W
Auswahl Gruppennummer (siehe Blockschaltplan)
2
reset settings
0
0
2
R/W
Works setting
0 = no function
1 = E+L basic settings
2 = preset internal value (default)
3
start service
0
0
199
R/W
Start a function
0 = no function
1 = reset controller
2 = save parameter
4
version
-
-
-
R
Software version
5
sensor adjust
6
sensitivity
5
1
40
R/W
Sensitivity in mg Fe
1 = max. sensitivity
40 = min. sensitivity (chapter 3.4)
7
amplification
5
1
15
R/W
Amplification stages to adjust amplifier to the sensing
head (to be modified only after consultation with E+L)
8
middle webspeed
130
3
199
R/W
Average web speed in m/min
In case of slow web speeds the value can be reduced
(Filter for fast signals, chapter 7.2).
9
web speed adjust
(chapter 7.4)
10
measurement
wheel
100
100
1999
R/W
circumference of measurement wheel in mm
11
imp./revolution
0
0
500
R/W
Pulse per revolution
0 = no transducer connected
12
output 1 adjust
(chapter 7.3)
13
normal - invers
1
0
1
R/W
Output1
0 = 24 V ON at signal
1 = 24 V OFF at signal (works setting)
14
pulse time
0
0
19,9
R/W
Duration of output impulse in s
0 = reset via input or key RESET
value > 0 = time after which signal output 1 will be
automatically reset
8. Parameters
8.1 Parameter listing MDS 50