CONFIGURATION MODE 4
Probe connected to input 3 with smart sensor
SM03E01ACC
if the smart sensor is disconnected or
to establish any communication between Smart
sensor and presence sensor then:
Obj "Temperature" is not send
Obj "Alarm" send "1"
18.
Thermostat behaviour on bus
failure, recovery and download
Behaviour on bus voltage failure
On failure of bus voltage no actions are executed by
the device; behaviour
of controlled actuators must
be set using their own parameters.
Behaviour on bus voltage recovery
On bus voltage recovery all the communication
objects are set to 0 except for objects for which a
parameter is defined for the initial value; thermostat
keeps these values in memory and restore them
after recovery:
Heat / Cool mode
HVAC Mode
Base Setpoint
Setpoint Adjustment
Force value in manual mode
Ventilation
Control values (i.e. commands to actuators) are
calculated using actual setpoint and temperature.
After power on device recalculates the
commands to actuators and switch them
on, if necessary, otherwise does not carry out any
action; you are recommended to set the behaviour
of actuator in order to switch the heating / cooling
equipment off after bus power on.
Behaviour on ETS Download
s possible to set initial value of:
Heat / Cool mode
HVAC Mode
Ventilation
For other communications objects the behaviour is
identical to bus voltage recovery.
Wrong application download
If the wrong ETS application is downloaded then
KNX/EIB led starts blinking and device is not
operative on the bus. A power reset must be done
or the correct ETS application must be downloaded.
19.
Logics
The logic functions are organized into groups of 3
objects: 2 inputs and 1 output, except the one
logic expression that will be described later.
The scheme of logics is as follows:
Inputs
Input datatypes can be bit, byte, float etc according
to the selected logic.
IN1 is always present. IN2 maybe unused (or hidden
directly by ETS).
Delay
The logic output can be delayed according to the
ETS parameter, if a new value is received, the output
is overwritten and the delay reset.
Cyclic
The delayed output can be retransmitted n times
according to ETS parameters
Logic function
LOGIC
FUNCTION
DELAY
CYCLIC
IN 1
IN 2
OUT