Appendix C: Applications
P/N 3102213-
EN • REV 006 • ISS 18FEB19
67
Figure 47: Typical redundant serial application
(1)
FW-UL6W, FW-
SP4I ca
rd, and FW-UL6CC1.
(2)
Primary serial connection to EST3 COM port 1. Limit connection to the same room, within 20 ft. (6.1 m) for UL
or 59 ft. (18 m) for ULC, and enclose in conduit or equivalent protection against mechanical injury.
(3)
Secondary serial connection to EST3 COM port 2. Limit connection to the same room, within 20 ft. (6.1 m) for
UL or 59 ft. (18 m) for ULC, and enclose in conduit or equivalent protection against mechanical injury.
Redundant Ethernet communication application
In a redundant Ethernet communication application, FireWorks uses two TCP/IP ports to connect to the fire alarm
system. If the primary port connection breaks, FireWorks can still communicate using the redundant port
c
onnection. See
Figure
48
.
Figure 48: Typical redundant Ethernet application
(1)
FW-UL6W and FW-UL6CC1.
(2)
Ethernet connection. Limit connection to the same room
, within 20 ft. (6.1 m) for UL or 59 ft. (18 m) for ULC,
and enclose in conduit or equivalent protection against mechanical injury.
(3)
MN-
FNSx Ethernet switch.
(4)
EST3/EST3X CPU and RS
-232 option card.
(5)
Other EST3/EST3X control panels in the same fire
alarm network.
(6)
Dashed line indicates the same enclosure (or equivalent).
(7)
EST3/EST3X RS
-
485 network.
(8)
Dedicated fiber network.
(2)
(3)
EST3
(1)
(4)
(3)
MN-COM1S
(1)
(8)
(3)
(2)
(5)
(4)
(3)
MN-COM1S
(6)
(6)
(8)
(7)
(7)
Summary of Contents for FireWorks FW-UL6S
Page 1: ...FW UL6W FireWorks Workstation Installation Manual P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 8: ...vi P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 20: ...Chapter 1 Introduction 12 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 36: ...Chapter 2 Installation 28 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 60: ...Chapter 4 UL ULC programming instructions 52 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 68: ...Appendix A System calculations 60 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 80: ...Appendix C Applications 72 P N 3102213 EN REV 006 ISS 18FEB19 ...