Configuring the FireWorks COM port
1.
On the System Builder Applications menu, click Communications Manager.
2. In the Communications Manager dialog box, select a port in the Ports list or click Add Port.
3. Under Port Properties, do the following:
In the Label box, type a label for the port.
Under Port Type, select Serial Port.
In the Assigned Node list, select the target node, and then check the Enabled check box.
In the Description box, type a description.
Under Serial Port properties, in the Com Port list, select the Lantronix CPR port.
4. Click Apply.
Testing the connection
Once the equipment is set up and deployed, you can use Lantronix CPR Manager to test the connection.
To test the connection:
1.
Start Lantronix CPR Manager.
2. In the navigation panel, click the COM port that you want to test.
3.
On the Com XX tab, set the serial port settings for the following values:
Baud Rate: 19200
Data: 8 bits
Parity: Even
Stop: 1 bit
Flow control: None
4. Click Open.
5
.
Verify that Com Status is Open and that the Network Status indicates you are connected to the correct IP
address.
6. Click Close.
Summary of Contents for FireWorks FW-UL6S
Page 1: ...FW UL6W FireWorks Workstation Installation Manual P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 8: ...vi P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 20: ...Chapter 1 Introduction 12 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 36: ...Chapter 2 Installation 28 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 60: ...Chapter 4 UL ULC programming instructions 52 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 68: ...Appendix A System calculations 60 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 80: ...Appendix C Applications 72 P N 3102213 EN REV 006 ISS 18FEB19 ...