Appendix C: Applications
66
P/N 3102213-
EN • REV 006 • ISS 18FEB19
Ethernet network application
FireWorks can communicate with EST3 and EST3X control panels over an Ethernet network (LAN or WAN).
Notes
•
When connecting FireWorks over a standard network to an EST3 or EST3X control panel with no firefighter
interface, the FireWorks connection is considered ancillary, meaning that it cannot have common controls
capability with the control panel.
•
When connecting FireWorks over a network to an EST3 or EST3X control panel that has a firefighter
interface, the FireWorks can have common controls capability with the control panel. This is a fire-only
UL/ULC proprietary application and is not suitable for UL/ULC security applications.
Figure 46 shows a typical Ethernet network application.
Figure 46: Typical Ethernet network application
(1)
FW-UL6W and FW-UL6CC1.
(2)
Ethernet connection. Limit connection to the same room, within 20 ft. (6.1 m) for UL or 59 ft. (18 m) for ULC,
and enclose in conduit or equivalent protection against mechanical injury.
(3)
MN-
FNSx Ethernet switch.
(4)
EST3/EST3X CPU card and RS
-232 option card.
(5)
Dedicated fiber network. See
MN-FNSx Fiber Optic Transceiver Module Installation Sheet
(P/N3102138
-
EN)
for distance and cable specifications.
(6)
Dashed line indicates the same enclosure (or equivalent).
Redundant communication applications
Redundant serial communications
In redundant serial communications, FireWorks uses two serial ports to connect to the fire alarm system. If the
primary port connection breaks, FireWorks can still communicate using the redundant port connection.
Figure 47 shows a redundant serial connection to the same control panel. For better survivability, connect the
primary port and the redundant port to separate control panels.
(4)
(3)
MN-COM1S
(1)
(5)
(3)
(2)
(6)
(4)
(3)
MN-COM1S
(6)
(4)
(3)
MN-COM1S
(6)
Summary of Contents for FireWorks FW-UL6S
Page 1: ...FW UL6W FireWorks Workstation Installation Manual P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 8: ...vi P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 20: ...Chapter 1 Introduction 12 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 36: ...Chapter 2 Installation 28 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 60: ...Chapter 4 UL ULC programming instructions 52 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 68: ...Appendix A System calculations 60 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 80: ...Appendix C Applications 72 P N 3102213 EN REV 006 ISS 18FEB19 ...