Chapter 2: Installation
P/N 3102213-
EN • REV 006 • ISS 18FEB19
27
Figure 25: Calibration target points
Connecting a PT-1S system event printer
Connect a PT-
1S printer to one of the USB ports. See
Figure 26.
Figure 26: USB printer connection
(1)
Supervised and power
-limited. Limit connections to the same room.
Notes
•
FireWorks only supervises the system event printer for loss of communication.
•
FireWorks does not differentiate between a printer that is turned off and a USB cable that is unplugged, and
does not provide supervision for “loss of power” and
“printer taken offline manually.”
•
FireWorks does not display a printer fault event until after another event occurs.
•
FireWorks will not recognize the system event printer automatically. You must add it to your FireWorks
project.