2.26
Programming Manual
than the default value is required, use the cursor control keys to move
the cursor to the correct number and press Enter.
After pressing Enter, the next screen is displayed:
Note:
California State Fire Codes allow a maximum of 30 seconds
alarm verification time. When installing in California, do NOT use
menu items 6) 35 seconds, 7) 45 seconds, or 8) 60 seconds.
Each of the ionization and photoelectric sensors entered as a group may
have a different alarm verification time associated with it. The cursor is
always located at the default value 1) None in the menu. If the default
setting is required, press Enter. If a setting other than the default value
is required, use the cursor control keys to move the cursor to the correct
number and press Enter.
The next window is used for selecting an Alternate Sensitivity Level
and/or Alternate Verification Time:
This alternate value will only be used for applications requiring
detectors to change sensitivity levels at a pre-selected time of day. If
this option is not going to be used, or a detector or group of detectors is
not going to alternate sensitivity levels, set the alternate sensitivity level
to the same value as the primary sensitivity level. Each detector may be
firealarmresources.com
Summary of Contents for IRC-3
Page 1: ...IRC 3 Programming Manual P N 250060 Revised 14JUL97 firealarmresources com...
Page 44: ...1 38 Programming Manual firealarmresources com...
Page 100: ...2 56 Programming Manual Typical Action Response firealarmresources com...
Page 142: ...3 30 Programming Manual firealarmresources com...
Page 144: ...firealarmresources com...
Page 146: ...firealarmresources com...
Page 148: ...firealarmresources com...
Page 150: ...firealarmresources com...
Page 152: ...firealarmresources com...
Page 154: ...firealarmresources com...
Page 156: ...firealarmresources com...
Page 158: ...firealarmresources com...
Page 160: ...firealarmresources com...
Page 162: ...firealarmresources com...
Page 164: ...firealarmresources com...
Page 166: ...firealarmresources com...
Page 168: ...firealarmresources com...
Page 170: ...firealarmresources com...
Page 172: ...firealarmresources com...
Page 174: ...firealarmresources com...
Page 176: ...firealarmresources com...
Page 178: ...firealarmresources com...
Page 180: ...firealarmresources com...
Page 182: ...firealarmresources com...
Page 184: ...firealarmresources com...
Page 186: ...firealarmresources com...
Page 188: ...firealarmresources com...
Page 190: ...firealarmresources com...
Page 192: ...firealarmresources com...
Page 194: ...firealarmresources com...
Page 196: ...firealarmresources com...
Page 198: ...firealarmresources com...
Page 200: ...firealarmresources com...
Page 202: ...firealarmresources com...
Page 204: ...firealarmresources com...
Page 228: ...firealarmresources com...
Page 232: ...firealarmresources com...
Page 234: ...firealarmresources com...
Page 236: ...firealarmresources com...
Page 238: ...firealarmresources com...
Page 240: ...firealarmresources com...
Page 242: ...firealarmresources com...
Page 244: ...firealarmresources com...
Page 245: ...IRC 3 Operations Manual P N 270180 Rev 3 5 14JUL97 firealarmresources com...
Page 250: ...iv Operations Manual firealarmresources com...
Page 283: ...firealarmresources com...