background image

CMU-24VDC-ITL Cabinet Monitor Unit 

Operations Manual 

Eberle Design Inc. 

Page 12 

A channel will be sensed active when the load current exceeds 105% of the Channel 

Current Sense Threshold programmed for that channel in the Datakey. A channel will not 

be sensed active when the load current is less than 95% of the Channel Current Sense 

Threshold programmed for that channel in the Datakey. A load current value between 95% 

and 105% of the Channel Current Sense Threshold may or may not be sensed active. This 

provides a hysterisis value of +/- 5% of the Channel Current Sense Threshold.  
The Channel Current Sense Threshold should be programmed for each monitored channel 

based on the minimum signal load under all worst case conditions. 

3.4 PDA CONTROL SIGNAL INPUTS 
3.4.1 LOCAL FLASH STATUS 

The cabinet should be wired such that operation of the cabinet in AUTO mode will place 

24VDC on the LF STATUS pin. Operation of the cabinet in FLASH mode should be open 

circuit on this input. This input will be considered active when the input voltage exceeds the 

Active threshold defined in Cabinet Control 5.1.  This input will not be considered active 

when the input voltage is less than the Not Active threshold defined in Cabinet Control 5.1. 

The CMU-24VDC will report the state of this input in the Type 189 frame. See section 2.9.

 

3.4.2 MAIN CONTACTOR (MC) COIL STATUS 

The cabinet should be wired such that the MC COIL STATUS input is connected to the 

24VDC  side of the main contactor signal bus relay coil. An active signal on this input 

indicates the Signal Bus should be powering the load switches. This input will be 

considered active when the input voltage exceeds the Active threshold defined in Cabinet 

Control 5.1. This input will not be considered active when the input voltage is less than the 

Not Active threshold defined in Cabinet Control 5.1. The CMU-24VDC will report the state 

of this input in the Type 189 frame.

 

3.4.3 MAIN CONTACTOR (MC) SECONDARY STATUS 

The cabinet should be wired such that the MC SECONDARY STATUS input will be 

connected to the output side of the main contactor signal bus relay. An active signal on this 

input indicates the Signal Bus is powering the load switches. This input will be considered 

active when the input voltage exceeds the Active threshold defined in Cabinet Control 5.1. 

This input will not be considered active when the input voltage is less than the Not Active 

threshold defined in Cabinet Control 5.1. The CMU-24VDC will report the state of this input 

in the Type 189 frame.

 

3.4.4 FTR COIL DRIVE STATUS 

The cabinet should be wired such that the FTR COIL DRIVE STATUS input is connected to 

the FTR COIL DRIVE signal in the DC SIGNAL POWER BUS. An active signal on this input 

indicates the flash transfer relays are energized and the field signals are driven from the 

load switch outputs. This input will be considered active when the input voltage exceeds the 

Active threshold defined in Cabinet Control 5.1. This input will not be considered active 

when the input voltage is less than the Not Active threshold defined in Cabinet Control 5.1. 

The CMU-24VDC will report the state of this input in the Type 189 frame.

 

3.4.5 CIRCUIT BREAKER (CB) TRIP STATUS 

The cabinet should be wired such that the CB TRIP STATUS input will be connected to the 

Auxiliary Switch output of the circuit breaker unit. The active state of this input indicates that 

the circuit breaker unit is not in the tripped state. This input will be considered active when 

the input voltage exceeds the Active threshold defined in Cabinet Control 5.1. This input will 

not be considered active when the input voltage is less than the Not Active threshold 

defined in Cabinet Control 5.1. The  CMU-24VDC  will report the state of this input in the 

Type 189 frame.

 

Summary of Contents for CMU-24VDC-ITL Series

Page 1: ...HIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE CMU 24VDC ITL SERIES ITS CABINET MONITOR UNIT REVISION OCTOBER 2008 pn 888 3912 002 CMU 24VDC ITL Low Voltage DC Cabinet Monitor Unit Operations Manua...

Page 2: ...No 7 246 037 Canadian Patent No 2 574 101 U S Pat No 9 460 620 MAINTENANCE NOTE THIS EBERLE DESIGN INC CABINET MONITOR UNIT HAS BEEN CAREFULLY INSPECTED AND TESTED TO ENSURE PROPER OPERATION IT IS REC...

Page 3: ...tus 6 2 9 1 Local Flash Status Recovery 6 2 10 Circuit Breaker Trip Status 6 2 11 Flasher Unit Output Failed Alarm 6 2 12 CMU Power Failure 7 2 12 1 24VDC Power Level Sense 7 2 12 2 Power Interrupt 7...

Page 4: ...CONFLICT Indicator 14 4 1 5 LACK OF SIGNAL Indicator 14 4 1 6 MULTIPLE Indicator 14 4 1 7 CU LOCAL FLASH Indicator 14 4 1 8 CLEARANCE Indicator 14 4 1 9 FIELD CHECK Indicator 14 4 1 10 SB 1 ERROR Indi...

Page 5: ...t is specially configured for low voltage 24Vdc DC signal loads 1 2 CHANNEL CONFIGURATION The CMU 24VDC can be configured to monitor up to 28 physical load switch channels of three inputs per channel...

Page 6: ...OFTWARE INTERFACE The front panel display of the CMU 24VDC provides limited operational status This status includes real time indicators for Power Serial Bus 1 activity Serial Bus 3 activity and eleve...

Page 7: ...sts longer than the minimum defined period the CMU 24VDC will enter the Failed State Action fault mode causing the OUTPUT relay to de energize and the contacts on the OUTPUT NO pins to open The cabine...

Page 8: ...are detected as concurrently active for less than 200 milliseconds the CMU 24VDC will not cause a LFSA When any conflicting channels are detected as concurrently active for 500 milliseconds or more t...

Page 9: ...the CMU 24VDC may or may not cause a LFSA The Current Sense Unit CSU monitor function is hardwired to the maximum of 28 physical channels thus Virtual Channels do not have CSU monitoring capability Th...

Page 10: ...ellow Change plus Red Clearance monitoring will be disabled when the MC COIL STATUS input is not active There is programming in the Datakey to disable Minimum Yellow Change plus Red Clearance interval...

Page 11: ...24VDC power supply inputs when either the POWERDOWN or NRESET input is False low When the POWERDOWN and NRESET signals are both False low the CMU 24VDC will cause a NFSA 2 12 3 POWER RECOVERY When th...

Page 12: ...CU in the Type 61 frame When a mismatch is detected while a Conflict Lack of Signal or Multiple fault is timing Field Check Status will be reported with the fault to indicate the faulty channel s and...

Page 13: ...illiseconds the monitor circuit will force a LFSA R and illuminate the DIAGNOSTIC indicator 2 15 RECURRENT PULSE DETECTION This error detection function supplements the normal Conflict Multiple and La...

Page 14: ...imum Recurrent Pulse detection can be disabled with the SEL1 option jumper see Section 2 15 1 2 15 1 RECURRENT PULSE DETECTION DISABLE The Recurrent Pulse Detection function can be disabled by solderi...

Page 15: ...ed to the 24VDC supply 3 2 LED SIGNAL LOAD ELECTRICAL REQUIREMENTS LED Signal loads shall meet the following requirements under all conditions of temperature time etc 1 the signal shall emit NO light...

Page 16: ...than the Not Active threshold defined in Cabinet Control 5 1 The CMU 24VDC will report the state of this input in the Type 189 frame 3 4 3 MAIN CONTACTOR MC SECONDARY STATUS The cabinet should be wire...

Page 17: ...100 msec and the OUTPUT relay energized Continuously activating the input will not affect CMU 24VDC operation The EXTERNAL TEST RESET input is intended for use in testing the CMU 24VDC and should not...

Page 18: ...ndicator will illuminate when the CMU 24VDC is in FSA as a result of a Lack of Signal Inputs fault See section 2 5 4 1 6 MULTIPLE INDICATOR A red MULTIPLE indicator will illuminate when the CMU 24VDC...

Page 19: ...m the main CMU 24VDC power supply and 48VDC Ground A Null Modem cable is required for connection to a standard PC port 4 3 RESET BUTTON Depressing the RESET button resets the CMU 24VDC from the FSA co...

Page 20: ...tive less than 19 5 Vrms DC Power Fail Monitor DC Power Level Sense Restore greater than 22 Vrms DC Power Level Sense Dropout less than 21 5 Vrms DC Voltage Monitors 24 Volt Monitor Active greater tha...

Page 21: ...00 ms Field Check Fault greater than 1000 ms No Fault less than 700 ms Typical 850 ms Local Flash Status Circuit Breaker Trip Fault greater than 450 ms No Fault less than 200 ms Typical 350 ms DC Powe...

Page 22: ...A17 PowerDown B17 PowerDown A18 SB3 TxData B18 SB3 TxData A19 SB3 RxData B19 SB3 RxData A20 SB3 Clock B20 SB3 Clock A21 LF Status B21 LF Status A22 Output Relay NO B22 Output Relay NO A23 CB Trip Stat...

Page 23: ...CMU 24VDC ITL Cabinet Monitor Unit Operations Manual Eberle Design Inc Page 19 Pin Function I O 5 Signal Ground 6 Reserved 7 Reserved 8 Reserved 9 Reserved...

Reviews: