background image

CMU-24VDC-ITL Cabinet Monitor Unit 

Operations Manual 

Eberle Design Inc. 

Page 5 

CMU-24VDC Power Fail resets the LFSA-R, the SB #3 timeout count will be reset to two, 

such that the next SB #3 timeout results in a LFSA-R. 
A SB #3 timeout failure during the programmed Minimum Flash time or during a CMU-

24VDC Power Failure will not cause a FSA.  

2.4 TYPE 62 FSA MESSAGE 

If the “N” bit is set in a Type 62 message, the CMU-24VDC will react by causing a NFSA. 

The NFSA will remain until the receipt of a Message 62 with the “N” bit cleared or until the 

CMU-24VDC is reset by a Unit Reset or CMU-24VDC Power Fail. The NFSA will last for 

the programmed Minimum Flash time at a minimum. 
If the “L” bit is set in a Type 62 message, the CMU-24VDC will react by causing a LFSA.  

2.5 LACK OF SIGNAL INPUTS MONITOR 

The CMU-24VDC will detect the absence of a required signal voltage on all the inputs of a 

channel OR the absence of any required channel load current. For voltage purposes a 

required signal on the Green OR Yellow OR Red inputs associated with a channel will be 

considered as that channel being Voltage Active. For load current purposes a total channel 

load current above the programmed threshold for a channel will be considered as that 

channel being Current Active. When a channel is not Voltage Active OR Current Active for 

less than 700 milliseconds, the CMU-24VDC will not cause a LFSA. When a channel is not 

Voltage Active OR Current Active for greater than 1000 milliseconds, the CMU-24VDC will 

cause a LFSA. When a channel is not Voltage Active OR Current Active for more than 700 

milliseconds but less than 1000 milliseconds, the CMU-24VDC  may or may not cause a 

LFSA. 
The Current Sense Unit (CSU) monitor function is hardwired to the maximum of 28 physical 

channels, thus Virtual Channels do not have CSU monitoring capability. The CSU monitor 

function must be disabled for any physical channel that has an input remapped to a Virtual 

Channel.  
Lack of Signal Input monitoring will be disabled for all channels when the MC COIL 

STATUS input is not active. There is programming in the Datakey to disable Lack of Signal 

Input monitoring on a per channel basis. 
Lack of Signal Input monitoring will also be disabled for any channel which has the DARK 

CHANNEL MAP bit set to "1" in the Datakey programming for the DARK CHANNEL MAP 

addressed by the DARK CHANNEL MAP SELECT bits in a Type 61 message. 

2.6 MULTIPLE INPUT MONITOR 

The CMU-24VDC will detect the presence of an active signal on two or more inputs of a 

channel. When the presence of an active signal on two or more inputs of a channel is 

detected for less than 200 milliseconds, the CMU-24VDC will not cause a LFSA. When the 

presence of an active signal on two or more inputs to a channel is detected for 450 

milliseconds or more, the CMU-24VDC will cause a LFSA. When the presence of an active 

signal on two or more inputs to a channel is detected for more than 200 milliseconds but 

less than 450 milliseconds, the CMU-24VDC may or may not cause a LFSA.  
Multiple Input monitoring may anticipate and prevent a possible conflicting signal display in 

the intersection in the event that a proceed signal on the current phase hangs up and is 

constantly detected as active. An open or no load condition (i.e., burned-out bulb) may be 

also detected as an active signal depending on the output impedance characteristics of the 

load switch (i.e. load switch leakage current), and may cause a Multiple Input Fault. 

Summary of Contents for CMU-24VDC-ITL Series

Page 1: ...HIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE CMU 24VDC ITL SERIES ITS CABINET MONITOR UNIT REVISION OCTOBER 2008 pn 888 3912 002 CMU 24VDC ITL Low Voltage DC Cabinet Monitor Unit Operations Manua...

Page 2: ...No 7 246 037 Canadian Patent No 2 574 101 U S Pat No 9 460 620 MAINTENANCE NOTE THIS EBERLE DESIGN INC CABINET MONITOR UNIT HAS BEEN CAREFULLY INSPECTED AND TESTED TO ENSURE PROPER OPERATION IT IS REC...

Page 3: ...tus 6 2 9 1 Local Flash Status Recovery 6 2 10 Circuit Breaker Trip Status 6 2 11 Flasher Unit Output Failed Alarm 6 2 12 CMU Power Failure 7 2 12 1 24VDC Power Level Sense 7 2 12 2 Power Interrupt 7...

Page 4: ...CONFLICT Indicator 14 4 1 5 LACK OF SIGNAL Indicator 14 4 1 6 MULTIPLE Indicator 14 4 1 7 CU LOCAL FLASH Indicator 14 4 1 8 CLEARANCE Indicator 14 4 1 9 FIELD CHECK Indicator 14 4 1 10 SB 1 ERROR Indi...

Page 5: ...t is specially configured for low voltage 24Vdc DC signal loads 1 2 CHANNEL CONFIGURATION The CMU 24VDC can be configured to monitor up to 28 physical load switch channels of three inputs per channel...

Page 6: ...OFTWARE INTERFACE The front panel display of the CMU 24VDC provides limited operational status This status includes real time indicators for Power Serial Bus 1 activity Serial Bus 3 activity and eleve...

Page 7: ...sts longer than the minimum defined period the CMU 24VDC will enter the Failed State Action fault mode causing the OUTPUT relay to de energize and the contacts on the OUTPUT NO pins to open The cabine...

Page 8: ...are detected as concurrently active for less than 200 milliseconds the CMU 24VDC will not cause a LFSA When any conflicting channels are detected as concurrently active for 500 milliseconds or more t...

Page 9: ...the CMU 24VDC may or may not cause a LFSA The Current Sense Unit CSU monitor function is hardwired to the maximum of 28 physical channels thus Virtual Channels do not have CSU monitoring capability Th...

Page 10: ...ellow Change plus Red Clearance monitoring will be disabled when the MC COIL STATUS input is not active There is programming in the Datakey to disable Minimum Yellow Change plus Red Clearance interval...

Page 11: ...24VDC power supply inputs when either the POWERDOWN or NRESET input is False low When the POWERDOWN and NRESET signals are both False low the CMU 24VDC will cause a NFSA 2 12 3 POWER RECOVERY When th...

Page 12: ...CU in the Type 61 frame When a mismatch is detected while a Conflict Lack of Signal or Multiple fault is timing Field Check Status will be reported with the fault to indicate the faulty channel s and...

Page 13: ...illiseconds the monitor circuit will force a LFSA R and illuminate the DIAGNOSTIC indicator 2 15 RECURRENT PULSE DETECTION This error detection function supplements the normal Conflict Multiple and La...

Page 14: ...imum Recurrent Pulse detection can be disabled with the SEL1 option jumper see Section 2 15 1 2 15 1 RECURRENT PULSE DETECTION DISABLE The Recurrent Pulse Detection function can be disabled by solderi...

Page 15: ...ed to the 24VDC supply 3 2 LED SIGNAL LOAD ELECTRICAL REQUIREMENTS LED Signal loads shall meet the following requirements under all conditions of temperature time etc 1 the signal shall emit NO light...

Page 16: ...than the Not Active threshold defined in Cabinet Control 5 1 The CMU 24VDC will report the state of this input in the Type 189 frame 3 4 3 MAIN CONTACTOR MC SECONDARY STATUS The cabinet should be wire...

Page 17: ...100 msec and the OUTPUT relay energized Continuously activating the input will not affect CMU 24VDC operation The EXTERNAL TEST RESET input is intended for use in testing the CMU 24VDC and should not...

Page 18: ...ndicator will illuminate when the CMU 24VDC is in FSA as a result of a Lack of Signal Inputs fault See section 2 5 4 1 6 MULTIPLE INDICATOR A red MULTIPLE indicator will illuminate when the CMU 24VDC...

Page 19: ...m the main CMU 24VDC power supply and 48VDC Ground A Null Modem cable is required for connection to a standard PC port 4 3 RESET BUTTON Depressing the RESET button resets the CMU 24VDC from the FSA co...

Page 20: ...tive less than 19 5 Vrms DC Power Fail Monitor DC Power Level Sense Restore greater than 22 Vrms DC Power Level Sense Dropout less than 21 5 Vrms DC Voltage Monitors 24 Volt Monitor Active greater tha...

Page 21: ...00 ms Field Check Fault greater than 1000 ms No Fault less than 700 ms Typical 850 ms Local Flash Status Circuit Breaker Trip Fault greater than 450 ms No Fault less than 200 ms Typical 350 ms DC Powe...

Page 22: ...A17 PowerDown B17 PowerDown A18 SB3 TxData B18 SB3 TxData A19 SB3 RxData B19 SB3 RxData A20 SB3 Clock B20 SB3 Clock A21 LF Status B21 LF Status A22 Output Relay NO B22 Output Relay NO A23 CB Trip Stat...

Page 23: ...CMU 24VDC ITL Cabinet Monitor Unit Operations Manual Eberle Design Inc Page 19 Pin Function I O 5 Signal Ground 6 Reserved 7 Reserved 8 Reserved 9 Reserved...

Reviews: