Function F96 Trigger/dial Mode
When an alarm Input is present the EDAC 222-02 will trigger. The EDAC 222-02 will not begin
calling until the trigger/dial time has passed (see function
F09
). Function
F96
is used to set the
units used (seconds or minutes) by the trigger/dial time in
F09
.
When the Input is
latching
the Input can be latched either at the trigger time or at the dial time
(see function
F52
).
Latch on trigger
means once the EDAC 222-02 has been triggered it will
continue until it is acknowledged. If the Input is set to
latch on dial
and the trigger is removed
before the dial has commenced the EDAC 222-02 will cancel and stop making calls. With function
F52
set as non-latching, the latch on trigger and latch on dial have no effect. The trigger dial time is
always relevant.
96
0
= Latch on trigger & trigger/dial time is in seconds.
1
= Latch on trigger & trigger/dial time is in minutes.
2
= Latch on dial & trigger/dial time is in seconds.
3
= Latch on dial & trigger/dial time is in minutes.
Default: 0 (Latch on trigger & trigger/dial time is in seconds)