EDAC 222-02 AUTO ALARM DIALLER
- 15 -
Exit to Run Mode
##
= Exit programming to RUN mode.
Once all these functions have been programmed, exit programming mode by pressing
##
very quickly at the
prompt. The EDAC 222-02 should now display the
with a
flashing dot. Pressing too slowly causes the display to cycle through the product software
version number before returning to the
prompt. This indicates that the unit is still in
programming mode. In RUN mode the EDAC 222-02 is ready to accept an Input trigger and
make alarm notification calls.
Testing the EDAC 222-02
By default the Input is set up for
normally open
.
Connecting the Input terminal to negative
supply will trigger the EDAC 222-02.
Use a paper clip or small peace of wire to connect any Input to
ground
(third terminal from
the left). This will make a closed connection, causing the Input to trigger and the EDAC
222-02 to make an alarm notification call.